Unit digit: Power failure storage selection
0: Store auxiliary frequency at power failure
The auxiliary frequency will be stored in FC.27 during power failure, and the
auxiliary frequency superposition polarity will be stored in FC.28.
1: Do not store auxiliary frequency at power failure
Do not store during power failure
Ten digit: Stop frequency processing
0: Hold auxiliary frequency after stop
Hold the auxiliary frequency during stop.
1: Clear the set frequency after stop
Clear the auxiliary frequency after stop
Note: During combined operation of the main frequency source and the auxiliary
frequency source, both have the same channel, and the auxiliary frequency source is
invalid.
FC.29
Stop timeout
0~6553.6s
10s
Refer to use instructions of F2.08 for detailed operation.
FC.30
Pulse
disconnection
detection time
0~6553.6s
0s
When FC.30 is 0, the pulse disconnection detection function is invalid. When FC.30 is
greater than zero, if the number of pulse data remains unchanged during the detection
interval of FC.30, the drive will decelerate and stop (deceleration time is 4). The function
DO17 outputs a fault signal, and the output fault signal is turned off at 10s after stop.
FC.31
Operation
panel
key
functions and locking
Select
000~422
000
This function defines the functions of M-F keys, STOP/RESET key and locking on the
operation panel.