EXPERT Standard Series User Manual
205
Use instructions of linkage function:
1. There are two linkage ratio channels, i.e. communication linkage ratio or AI2 linkage
ratio, which are selected by the hundred digit of function code FC.33.
2. The gain of communication linkage ratio is set by function code Fb.06.
3. When the gain of AI2 linkage ratio is 100%, the corresponding reference voltage is
set by function code F5.10, and the actual gain is the ratio of the external given AI2 voltage
to the reference voltage.
4. The maximum gain of acceleration/deceleration linkage ratio is limited to 5 times;
the gain of frequency linkage ratio is not limited, but the final output frequency is limited by
the upper or lower frequency limit.