EXPERT Standard Series User Manual
41
GND
+10V power
common
terminal
Analog signal and reference
ground of +10v power supply Mutual inner isolation shall
be produced between COM
and GND
COM
+24Vpower
common
terminal
Input/output public terminal
of digital signal
+24V
+24V power
supply
Digital signal power supply
Max output current:200mA
PLC
Multi-function
input public
terminal
DI1—DI5 public terminal
Short circuit with 24v as
factory default
CME
Digital output
common
terminal
Multi-function output terminal
DO1,DO2 common terminal
Short circuit with COM as
factory default
2.5.3 The wiring of analog input
The terminals of AI1 and AI2 accept the input of analog signal .Input voltage (0~
10V)or input current (0 ~ 20mA)are selected by the function code of
F5.12.Terminal wiring as follows diagram2-18
Diagram2-21 Wiring for analog input terminal
2.5.4 Drive control circuit wiring