EXPERT Standard Series User Manual
60
Parameter
code
Parameter
name
Setting range
Mini
munit
Default
value
Mod
ition
F6.13
Relay output function
selection (TA/TB/TC)
26:Output voltage(0~1.2*Ve)
27:DC Bus voltage(0~800V)
28:AI1(0~10V/0~20mA)
29:AI2(0~10V/0~20mA)
30:Output power(0~2*Pe)
31:Upper computer percentage(0~
1000)
32:Expansion card AI3(-10~10V)
1
16
×
F6.14
FDT1 level
0.00~550.0Hz
0.01Hz 50.00Hz
○
F6.15
FDT1 lag
0.00~550.0Hz
0.01Hz 1.00Hz
○
F6.16
FDT2 level
0.00~550.0Hz
0.01Hz 25.00Hz
○
F6.17
FDT2 lag
0.00~550.0Hz
0.01Hz 1.00Hz
○
F6.18
Frequency reaches
(FAR) detection
width
0.00~550.0Hz
0.01Hz 2.50Hz
○
F6.19
Reserved
-
-
0
○
F6.20
DO2 maximum
output pulse
0.1~50.0kHz
0.1k
10.0k
○
F6.21
Counter reset value
setting (Setting count
value reached given
value)
F6.22~9999
1
0
○
F6.22
Counter detection
value setting
(Setting count value
reached given
value)
0~F6.21
1
0
○
F6.23
Terminal positive
and negative logic
Binary system setting
0:Breakover effective
1:Disconnect effective
LED units digit:
BIT0~BIT3:DI1~DI4
LED tens digit:
BIT0~BIT3:DI5~DI8
LED hundreds digit:
BIT0~BIT1:DI9; DI10
BIT2~BIT3:DO1; DO2
LED thousands digit:Reserved
1
0000
○