EXPERT Standard Series User Manual
76
Parameter
code
Parameter
name
Setting range
Mini
munit
Default
value
Mod
ition
FA.07
Protective action
selection 0
LED units digit:Alarming function
selection
0:No action
1:Auto alarm reset and not run
FA.09
Automatic reset
times
0~10,0 shows no automatic reset
function
Note: Module protection and
external device fault has no reset
function.
1
0
×
FA.10
Automatic reset
interval time
2.0~20.0s
0.1s
5.0s
×
FA.11
Overload pre-alarm
detection setting
LED units digit:Action selection
0:Detecting all the time
1:Detect only in constant speed
LED tens digit:Alarming selection
0:No alarming, continue to run
1:Alarm, halt
LED hundreds digit:Detection
quantity selection
0:Relative to motor rated
current(E008)
1:Relative to drive rated
current(E009)
1
000
×
FA.12
Overload pre-alarm
detection level
20.0%~200.0%
0.1% 130.0%
×
FA.13
Overload pre-alarm
detection time
0.0~60.0s
0.1s
5.0s
×
FA.14
Protective action
selection 1
LED units digit:Undervoltage fault
indication action selection
0:No action
1:Action (regard undervoltage as
fault)
LED tens digit:reserved
LED hundreds digit:reserved
LED thousands digit:Default phase
action selection
0:Both input and output default
phase are protected
1:Input default phase no action
2:Output default phase no action
3:Both input and output default
phase no action
1
0000
×