Chapter 6 Detailed Description of Parameter Use
6.1 Group F0 system management parameters
F0.00
Parameter write protection
0~2
0
The settings of this function code determine the protection level of the drive
parameters, namely:
0: All parameters are allowed to be rewritten;
1: Except the set frequency (F1.07) and this function code, other function code
parameters are not allowed to be rewritten;
1: Except this function code, other function codes are not allowed to be rewritten.
Note: When leaving the factory, the function code parameter is 0, and any
parameter is allowed to be modified by default; if only the operating frequency can be
modified, and other function codes cannot, set this function code to 1. The user can set this
function code to the expected protection level as needed.
F0.01
Multi-function keys
selection
0~3
0
To set this function code, select the specific functions of multi-function keys M-F.
0: Jog function
1: Remote switch function: 485 communication communicates with the upper
computer (not save at power failure)
2: Forward and reverse shift (not save at shutdown)
3: Clear the frequency increment set by UP/DOWN.
Note: This function code is restricted by FC.31.
F0.02
Parameter initialization
0~2
0
0: No operation
1: Reserved
2: Restore factory parameters
When this function code is saved into parameter 2, the function code parameters
except group F0, group FF, F1.08, F3.00~F3.11, and F7.06 will be restored to factory
parameters according to model.
After clearing memory information or restoring to factory parameters, this function
code will automatically restore to 0.