382095 V4.1 7/06
20
The phase angles of V2, V3, I1, I2, and I3 are displayed with respect to V1.
V1, V2, V3, I1, I2, I3, V12, V23, and V31 are displayed in vector form graphically.
V1, V2, V3: Phase voltages in phase format with respect to V1
I1, I2, I3: Line currents in phase format with respect to V1.
IVn: Calculated voltage and current of the neutral with respect to ground.
V12, V23, V31: Line voltage in phase format with respect to V1.
Ave: Average of line voltage V12, V23, and V31 and line current I1, I2, and I3
dV%: Historical maximum % value of (Max (V1, V2, V3) – Min (V1, V2, V3)) / Min (V1, V2, V3) * 100%
VUR: Voltage (Unbalanced Ratio)
d02: The first number is Zero Sequence Unbalanced Ratio in % (d0) of voltage; the second number is the
Negative Sequence Unbalanced Ratio in % (d2) of voltage. When VUR is displayed before d02, d02
represents the Zero and Negative Sequence Unbalanced Ratios for voltage.
REF: nominal voltage for transient detection reference
Sd%: threshold in % for transient detection with respect to nominal voltage (REF).
NOTE: The phase is drawn only when the reading exceeds 200 counts. If V is zero, the phase of the current
will not be drawn.
Press this button to change the display from VUR to IUR
dA%: Historical max % value of (Max (I1, I2, I3) – Min (I1, I2, I3) ) / Min (I1, I2, I3) * 100%
IUR: Current Unbalance Ratio
d02: The first number is Zero Sequence Unbalanced Ratio in % (d0) for current; the second number is the
Negative Sequence Unbalanced Ratio in % (d2) for current. When IUR is displayed before d02, d02
represents the Zero (d0) and Negative (d2) Sequence Unbalanced Ratios for current.
REF: Nominal voltage for transient detection reference
Sd%: Threshold in % for transient detection with respect to nominal voltage (REF).
NOTE: If the voltage of L1, L2, and L3 is not connected in the correct sequence, the analyzer will show
L1-3-2 in the right top corner, and it will beep to warn of an incorrect phase sequence.