User's Manual 

 

 

 

 

Earth Ground Resistance Tester 

 

Model 382152

 

 

 

 

 

 

 

 
 

 

 
 

 

 

 
 

 

 

 
 

 

 

 
 

 

 

 

Introduction 

Congratulations on your purchase of the Extech Earth Ground Resistance Tester. This 

device can measure resistance (in 3 ranges) and AC voltage to 200V. 2mA constant 

current test signal permits earth resistance tests without tripping current breakers in the 
circuit under test. Single, momentary tests or automatic 3-minute tests can be selected. 

This device was designed to meet IEC-1010 (EN 61010) safety standards. 

Earth Ground Resistance Testers are useful for: 

• 

Estimating ground resistance of a proposed substation or transmission tower. 

• 

Computing inductive coupling between neighboring power and communication 

circuits. 

• 

Designing cathode protection systems. 

• 

Geological surveys. 

Careful use of this meter will provide years of reliable service. 

 

Summary of Contents for 382152

Page 1: ...urrent breakers in the circuit under test Single momentary tests or automatic 3 minute tests can be selected This device was designed to meet IEC 1010 EN 61010 safety standards Earth Ground Resistance Testers are useful for Estimating ground resistance of a proposed substation or transmission tower Computing inductive coupling between neighboring power and communication circuits Designing cathode ...

Page 2: ...not be liable for any direct indirect incidental or consequential damages Extech s total liability is limited to repair or replacement of the product The warranty set forth above is inclusive and no other warranty whether written or oral is expressed or implied Safety Please read the following safety information carefully before attempting to operate the meter and use the meter only as specified i...

Page 3: ... as most significant digit Safety IEC 1010 EN 61010 category III Weight 27 7oz 800g with batteries Dimensions 6 42 x 3 94 x 2 163 x 100 x 50 mm Supplied accessories Test leads 3 auxiliary earth bars 2 six AA batteries and carrying case Range Specifications Measurement Range Resolution Accuracy Earth Ground Resistance 2mA test current 820Hz 20 200 2000Ω 0 01Ω 0 1Ω 1Ω 2 rdg 2 d Earth Voltage Frequen...

Page 4: ...ltage Test 1 Set the meter s function switch to the ACV position 2 Press the PUSH ON button to perform a single momentary test 3 Press the PUSH ON and TIMER ON buttons simultaneously to begin a 3 minute test The 3 minute test automatically shuts down after 3 minutes Press the Timer OFF button to end an automatic test at any time 4 The front panel test status LED will light if the test is operating...

Page 5: ...ng correctly If the LED does not light check for problems such as open circuits or overload conditions 5 If high resistance is detected note the value and take appropriate steps to correct the ground connection if necessary 6 Readings between 300 to 600Ω in the 2kΩ range are typical when the test leads are not connected to the meter Data Hold Data Hold freezes the latest measurement reading on the...

Page 6: ...age Periodically wipe the meter s case with a damp cloth and mild detergent do not use abrasives or solvents If the meter is not to be used for a period longer than 60 days remove the batteries and store them separately Calibration and Repair Services Extech offers complete repair and calibration services for all of the products we sell For periodic calibration NIST certification or repair of any ...