iSOLATE501 Operating Manual
Page 5 of 21
2 Safety Information and Notes
2.1
Storage of this Manual
Keep this user manual safe and in the vicinity of the device. All persons who have to
work on or with the device should be advised on where the manual is stored.
2.2
Special Conditions for Safe Use
2.2.1 ATEX/IECEx
2.2.1.1 The RF power input to the device must be limited to defined power levels
dependent on the Equipment/Gas Group:
Maximum safe input power, defined as in
normal operation without user-settable
software limits, and must include antenna
gain consideration.
Group I
6.0W (37.7 dBm)
Group IIC
2.0W (33 dBm)
Group IIB
3.5W (35.4 dBm)
Group IIA
6.0W (37.7 dBm)
Group III
6.0W (37.7 dBm)
2.2.1.2 The product must be mounted such that it is earthed before use in accordance
with clause 15 in IEC 60079-0:2011.
2.2.1.3
The product shall be mounted in an IECEx / ATEX approved Ex ‘n’ or Ex ’e’
enclosure with minimum IP54 rating while situated in hazardous gas
atmospheres.
2.2.1.4
The product must be mounted in an IECEx / ATEX approved Ex ‘n’ or Ex ’e’
enclosure with minimum IP54 rating while situated in hazardous dust
atmospheres.
2.2.1.5 Live connections or disconnections in the hazardous area are limited to a passive
antenna type only. Antenna output is galvanically isolated, so intrinsically safe
parameters are not relevant.
Summary of Contents for iSOLATE501
Page 1: ...Operating Manual iSOLATE501...
Page 10: ...iSOLATE501 Operating Manual Page 10 of 21 Figure 1 Earthing and Mounting of iSOLATE501...
Page 11: ...iSOLATE501 Operating Manual Page 11 of 21 Figure 2 iSOLATE501 Dimensions...
Page 14: ...iSOLATE501 Operating Manual Page 14 of 21 Figure 3 Electrical Installation...
Page 20: ...iSOLATE501 Operating Manual Page 20 of 21 7 EU Manufacturers Declaration...