Operating Manual
49
•
Level SOC 1 active {1439} {1442}
•
Level SOC 1 {1440} {1443}
•
Duration 1 {1581} {1590}
•
Level SOC 2 active {1582} {1591}
•
Level SOC 2 {1583} {1592}
•
Duration 2 {1584} {1593}
•
Level SOC 3 active {1585} {1594}
•
Level SOC 3 {1586} {1595}
•
Duration 3 {1587} {1596}
•
Level SOC to deactivate the auxiliary contact {1441} {1444}
•
Duration on level for deactivation {1588} {1597}
•
Deactivate if the battery is in floating phase {1589} {1598}
8.1.1.10 Security : Limit the time of activation {1512} {1513}
Caution :
If the maximum duration for the relay activation that you have selected is
reached and if the activation conditions are still present (for instance a
battery undervoltage), the contact will not be reactivated as long as the
conditions are present. Therefore there is a risk that the auxiliary contact
remains locked in this deactivated state and you will have to reset manually
this alarm by deactivating and then activating this parameter.
Use this function with care and only as a security.
8.1.1.11
Maximum duration of activation {1514} {1515}
When the conditions are met, either one or two relays are activated permanently. If
you wish that the activation duration is limited in time, even if the conditions are met,
you can activate this function. Once the relay is activated, a countdown runs
according to the duration you have selected. Once this countdown is completed the
relay is released, even if the conditions are still there. The relay can not be anymore
activated as long as the activation conditions have not disap-peared.
8.1.1.12 Reset all settings {1569} {1570}
This function serves to reset all previous settings done on the corresponding auxiliary
contact. Once this operation done, the auxiliary contact is not activated anymore.
Caution: this function cannot be cancelled.
Use this function before programming any function for an auxiliary contact.
By doing this way you are sure that you begin with no unexpected setting
who can activate the contact.
8.1.2
AUXILIARY CONTACTS 1 AND 2 EXTENDED FUNCT. {1489}
8.1.2.1 Generator startup
The two contacts may be combined in order to automatically start up a generator
equiped with an electric starter. In this case the two contacts are dedicated to this
function.
Auxiliary contact 1 serves as an operational contact and auxiliary contact 2 as a
startup contact.
Summary of Contents for iUPS101
Page 1: ...Installation Operating Manual iUPS101...
Page 55: ...Operating Manual 55...
Page 59: ...Operating Manual 59 11 5System Assembly Details...
Page 62: ...Operating Manual 62 14 Certification 14 1Atex Label...
Page 63: ...Operating Manual 63 14 2Atex Certificate...
Page 64: ...Operating Manual 64...
Page 65: ...Operating Manual 65...
Page 66: ...Operating Manual 66...
Page 67: ...Operating Manual 67...
Page 68: ...Operating Manual 68 14 3iUPS101 EC Declaration of Conformity...
Page 69: ...Operating Manual 69 14 4UPS System EC Declaration of Conformity...