Operating Manual
56
11 Technical Data
11.1 Specification
Input Mains Power Supply
230V iUPS101: 180-265VAC (45-65Hz)
120V iUPS101: 90-150VAC (55-75Hz)
Output Power Supply
230VAC or /- 2%, 50/60 Hz
Maximum Power Output
3KVA - See de-rating table
Backup Time
For full load, approx 39 minutes @ 20
o
C or 87 minutes with
additional battery enclosure. See system run time table for
further details. Based on iBATT100 enclosure
Input Battery Voltage
24V / 48V
Alarm Output
2 x Programmable volt free alarm contacts, energised on a
general alarm condition
AC rating: 230V/12A
DC rating: 24V/4A, max 50V/3A
Ingress Protection
Ex’d’ Enclosure - IP66
Ex’e’ Close Coupled Enclosure - IP66
Ex’e’ Battery Enclosure - IP45 (Non Ex rating) / IP23 (Ex rating)
Weight
Ex’d’ Enc Ex’e’ Close Coupled Enclosure - 90Kg
Ex’e’ Battery Enclosure - 122Kg
Environmental
Operating temperature: –20
o
C to 55
o
C @500VA
See ambient de-rating table for further details
Relative humidity; 0 to 95%, non condensing
ATEX Certification
ATEX II 2 G Ex d[e] e IIB T5 Gb
EMC
EN61000-6-4:2007, EN61000-6-2:2005
Mean Time Between Failure
(MTBF)
340 000 hrs/failure
Table 7.0
Summary of Contents for iUPS101
Page 1: ...Installation Operating Manual iUPS101...
Page 55: ...Operating Manual 55...
Page 59: ...Operating Manual 59 11 5System Assembly Details...
Page 62: ...Operating Manual 62 14 Certification 14 1Atex Label...
Page 63: ...Operating Manual 63 14 2Atex Certificate...
Page 64: ...Operating Manual 64...
Page 65: ...Operating Manual 65...
Page 66: ...Operating Manual 66...
Page 67: ...Operating Manual 67...
Page 68: ...Operating Manual 68 14 3iUPS101 EC Declaration of Conformity...
Page 69: ...Operating Manual 69 14 4UPS System EC Declaration of Conformity...