background image

19

ENGLISH

- Insert the standard key (Figures 19 a) or the personalised

key (Figures 19 b) in the lock and 

turn anticlockwise 

by

one revolution.

- Open or close the barrier manually.

7. RETURNING TO NORMAL OPERATION

To prevent an accidental impulse from activating the
barrier, turn off the system’s electrical power supply before
returning to normal operation.
triangular key (standard):
- turn the key 

clockwise 

until it stops, then remove it (Fig.

19a).
personalised key (optional):
- turn the key 

clockwise 

until it stops.

- turn the key 

anticlockwise 

very slowly to the point where

it can be removed (Fig. 19 b).

8. MAINTENANCE

When performing maintenance always check that the by-
pass screws are set correctly, that the system is balanced
and that the safety devices operate correctly.

8.1. TOPPING UP WITH OIL

Check periodically the quantity of oil inside the tank.
For medium/low duty cycles a yearly check is sufficient; for
more severe operation it is advisable to check every 6
months.
The level must not fall below the level mark on the inspection
window (Fig. 20).
To top up, unscrew the filler cap (Fig. 20) and pour in oil up
to the correct level.
Use exclusively FAAC XD 220 oil.

Fig. 19 a

BLOCCA / LOCK

BLOQUE / VERRIEGELT

BLOQUEAR

SBLOCCA / UNLOCK

DEBLOQUE / ENTRIEGELT

DESBLOQUEAR

BLOCCA / LOCK

BLOQUE / VERRIEGELT

BLOQUEAR

SBLOCCA / UNLOCK

DEBLOQUE / ENTRIEGELT

DESBLOQUEAR

Fig. 19 b

Fig. 20

8.2. BLEEDING AIR FROM THE HYDRAULIC CIRCUIT

If the beam moves in an irregular manner, this may be due
to the presence of air in the hydraulic circuit:
1)

Remove the breather screw (Fig. 9).

2)

Actuate the beam electrically:
- while the beam is opening, slightly loosen the bleed

screw on the piston with balance spring, then
retighten it (Fig. 1, pos. 33);

- while the beam is closing, slightly loosen the bleed

screw on the piston without balance spring, then
retighten it (Fig. 1, pos. 11).

If necessary, repeat this operation, until you obtain a
smooth beam movement.

9.  REPAIRS

For repairs, contact an authorised FAAC Service Centre.

10. ACCESSORIES

OPTIONAL ELECTRONIC BOARDS

The three boards - SLAVE, FSW and RELAY - provide
supplementary functions for the 624MPS unit, and may be
used simultaneously.
Carefully read the instructions supplied with each product.

624 FSW board (Fig. 21)

The 624 FSW board manages the operation of photocells
in P logic (Parking).
To prevent trespassing, the closing safety device causes
the beam to stop, then to close again on disengagement.

624 SLAVE BOARD (Fig. 21)

The SLAVE board manages the simultaneous operation of
two opposing barriers.
One of the two barriers is identified as MASTER, the other
one as  SLAVE.

Fig. 21

Summary of Contents for 620 STANDARD

Page 1: ...lich 100 Altpapier pour la nature papier recyclé 100 for nature recycled paper 100 per la natura carta riciclata 100 para la naturaleza 100 papel reciclado 620 640 642 624 MPS C ERME T A Z I E N D A C E R TIF I C A T A UNI EN ISO 9001 085 ...

Page 2: ...p A Bologna 20 de diciembre de 1995 Presidente Administrador Delegado KONFORMITÄTSERKLÄRUNG NACH ISO IEC NORM RICHTLINIE 22 EN 45014 HERSTELLERNAME FAAC S p A HERSTELLERANSCHRIFT FAAC S p A Via Benini 1 40069 Zola Predosa BOLOGNA ITALY Hiermit erklären wir eigenverantwortlich daß die Produkte Modelle Serie 402 422 400 750 760 746 844 820 860 590 1 593 580 595 550 500 RC 503 RC 560 630 620 640 642 ...

Page 3: ... subsequent amendments 91 368 EEC 93 44 EEC and 93 68 EEC complieswiththeessentialsafetyrequirementsinthefollowingEECDirectives 73 23 EEC and subsequent amendment 93 68 EEC 89 336 EEC and subsequent amendments 92 31 EEC and 93 68 EEC and furthermore declares that unit must not be put into service until the machinery into which it is incorporated or of which it is a component has been identified an...

Page 4: ... shall be provided for the installation with an opening distance of the contacts of 3 mm or more Alternatively use a 6A thermomagnetic breaker with multi pole switching 13 Ensure that there is a differential switch up line of the electrical system with a trip threshold of 0 03A 14 Check that the earthing plant is in perfect condition and connect it to the metallic parts Also earth the yellow green...

Page 5: ...ndcablepassagehole 19 Anchor bolt 20 Baseplate 21 Right handcablepassagehole 22 Earth connector fixing screw 23 Cablepipe 24 624 MPS electronic control unit 25 Right handconnectingpipe 26 Unlocking lever 27 Support position for 460 mm spring 28 Air intake grille 29 Right handpiston 30 Support position for400 mm spring 31 Balancespringsupport 32 Balancespring 33 Right handpistonbleedscrew 34 Therma...

Page 6: ... automation system make sure that the following requirements are met During its movement the beam does not strike against obstacles or overhead power cables The characteristics of the ground must ensure sufficient support for the foundation plinth There must be no pipes or electrical cables in the area to be dug for installing the foundation plinth If the housing is located in a vehicle transit ar...

Page 7: ...alled with the door on the premises side 2 Set up the operator for manual operation as described in section 6 Fig 8 3 Remove the two breather screws as shown in Figure 9 and keep them in a safe place 4 Assemble the beam using the screws supplied as shown in Figures 10 and 10 b Apply the cap to the hole 620 only The rubber edged side of the beam must be in the closing direction 5 Adjust the mechani...

Page 8: ...SORIES LED ON contact closed OFF contact open FCC closing limit switchnot engaged closing limit switch engaged FCA opening limit switchnot engaged opening limit switch engaged OPEN activated deactivated CLOSED FSW activated saf disengaged deactivated saf engaged STOP deactivated activated ALARM beammoving beamstationary WARN LIGHT see warn light operation see warn lightoperation POWER motor power ...

Page 9: ...ec the closing movement is reversed at once ALARM CONDITION It arises in the following cases 1 Enabling of anti panic input 2 Activation of safety TIME OUT device which interrupts the operation of the system when operating time exceeds 30 sec 3 Simultaneous triggering of the two limit switches 4 Microprocessor reading anomaly syncro The alarm condition is indicated by the quick flashing 0 25 sec o...

Page 10: ...m away from the limit switch 3 Re lock the system see paragraph 6 and carry out a few test cycles in order to check whether the positioning of the limit switches the balancing of the spring and the transmitted torque are correct 5 4 TESTING THE AUTOMATION SYSTEM Once installation is complete affix the danger warning adhesive on the top of the housing Fig 18 Carry out a thorough functional check of...

Page 11: ...EGELT BLOQUEAR SBLOCCA UNLOCK DEBLOQUE ENTRIEGELT DESBLOQUEAR BLOCCA LOCK BLOQUE VERRIEGELT BLOQUEAR SBLOCCA UNLOCK DEBLOQUE ENTRIEGELT DESBLOQUEAR Fig 19 b Fig 20 8 2 BLEEDING AIR FROM THE HYDRAULIC CIRCUIT If the beam moves in an irregular manner this may be due to the presence of air in the hydraulic circuit 1 Remove the breather screw Fig 9 2 Actuate the beam electrically while the beam is ope...

Page 12: ...e skirt kit is fitted the balance spring must be adjusted ARTICULATION KIT Fig 25 mod 620 only The articulation kit makes it possible to articulate the rigid beam to a maximum ceiling height of 3 m IMPORTANT If the articulation kit is fitted the balance spring must be adjusted END FOOT Fig 26 The end foot supports the beam in closed position and prevents it from bending downwards IMPORTANT If the ...

Page 13: ...mounted in an enclosure which assures adequate protection against atmospheric agents and can be fitted inside the housing The normal position of the beam is closed in a horizontal position When the electronic control unit receives an opening command from the remote radio control or any other control device it activates the hydraulic system and causes the beam to rotate upwards by 90 to the vertica...

Reviews: