Summary of Contents for E012

Page 1: ...E012 E012 ...

Page 2: ...n sur les remarques concernant les caractéristiques ou le fonctionnement du produit Vor der Installation des Produkts sind die Anweisungen vollständig zu lesen Mit dem Symbol sind wichtige Anmerkungen für die Sicherheit der Personen und den störungsfreien Betrieb der Auto mation gekennzeichnet Mit dem Symbol wird auf Anmerkungen zu den Eigenschaften oder dem Betrieb des Produkts verwiesen Lean com...

Page 3: ...s manufactured by FAAC S p A Bologna 01 December 2006 The Managing Director A Bassi Contents 1 INSTALLATION OF CONTROL UNIT 4 2 ELECTRICAL CONNECTIONS 5 2 1 ELECTRICAL SYSTEM LAY OUT 5 2 2 DESCRIPTION OF CONTROL UNITS 5 2 2 1 TECHNICAL SPECIFICATIONS 5 2 2 2 PRESENTATION OF THE BOARD 6 2 2 3 POWER SUPPLY CONNECTION 7 2 3 ELECTRICAL WIRING FOR BOARD AND MOTORS 8 2 3 1 AN ESSENTIAL CONTROL 10 2 4 WI...

Page 4: ...d pulse generators will then be connected on the side of the gate supplied with 230V current which must be connected to the toroidal transformer to change it to 13V and near to the operator Route the electrical cables in the lower part of the enclosure using adequate rigid tubes and or hoses and appropriateconnections Leave the cables inside the enclosure lengthy enough to enable you to wire up Se...

Page 5: ...N CONTROL BOARD Power supply voltage of the toroidal transformer 230V 50 60Hz Power supply voltage of the control unit 13V 50 60Hz Absorbed power 7 W Motor max load 50 W per motor Accessories max load 12 Vdc 150mA Flashing light max load 12 Vdc 21W max Operatingtemperature 20 C 55 C Protective fuse 2 Function logics Automatic Step by step automatic Step by step semiautomatic Programming of functio...

Page 6: ... Terminal Connect the earthing cable to this terminal The earthing cable must be connected to the earthing system of the 230V power supply line The connection is absolutely necessary for correct operation of the control unit TERMINAL BOARD CN2 motors Terminals 7 8 OPM1 CLM1 The motor power cable must be connected to these terminals For two motor installations the power cable of the motor which ope...

Page 7: ...lled by LED FSW This contact can be disabled with dip switch 6 see paragraph 2 5 1 If you decide to disable the photocells you do not have to jumper the input The control unit is supplied with the photocell input disabled Terminals 17 18 STOP COM1 Normally closed contact Connect to these terminals any pulse generator push button key selector etc which by opening a contact immediately stops the gat...

Page 8: ...om the dwelling to the pilaster B The terminal with fuse inserted in the enclosure is used for connecting the 230 V mains supply to the primary winding of the toroidal transformer For the connection respect the indications in the figure C 12 Vdc power supply from toroidal transformer D BROWN E BLUE F YELLOW GREEN BROWN BLUE BROWN BLUE RED RED YELLOW GREEN BROWN BLUE BROWN BLUE The figure shows an ...

Page 9: ... THE INSIDE A 230 Volt Mains power supply coming from the electrical panel of the dwelling Protected by a differential switch or by a 10 Amp fuse 3 x 1 5 mm2 line from the dwelling to the pilaster B The terminal with fuse inserted in the enclosure is used for connecting the 230 V mains supply to the primary winding of the toroidal transformer For the connection respect the indications in the figur...

Page 10: ... you decide to disable these commands you do not have to jumper the input This control is essential otherwise the motor will not start IMPORTANT The dip switch cursors are shown in white in the following drawings 2 4 WIRING OF OPTIONAL ACCESSORIES BATTERIES TOROIDAL TRANSFORMER POWER SUPPLY TO EXTERNAL ACCESSORIES EARTH MOTOR 1 MOTOR 2 ELECTRIC LOCK 12V FLASHING LAMP COURTESY LIGHT RECEIVER OTHER ...

Page 11: ...arity indicated on the board A maximum of two 12 Vdc 1 2 Ah batteries connected in parallel can be connected to the control unit Power supply provided by the batteries should be considered an emergency situation The number of possible manoeuvres depends on the quality of the batteries the gate s structure weight dimensions condition of the pivot etc and on the time since power was cut etc BROWN BL...

Page 12: ...s disabling all automatic functions This is because when the clutch operates twice consecutively it means that the obstacle is still present and it could be dangerous to perform any other manoeuvre When the obstacle has been removed give a START pulse and the control unit will resume the memory stored cycle If the clutch operates three consecutive times and for more than 120 seconds the control un...

Page 13: ...closing 5 Make sure that both leaves perform the closing manoeuvre and that the leaf with motor M2 moves first If this does not happen stop gate movement with a RESET pulse jumper connecting the two RESET pins to each other and using the connector see figure 6 Cut the power supply and take the connector back to its normal position see figure 7 Make the suitable corrections to the motor connections...

Page 14: ...ATE STATUS PULSES Closed Openinpause Closing Opening OPEN A Opens leaves and re closes after pause time Closes at once Stops gate motion and at next pulse opens Stops gate motion and at next pulse closes OPEN B Partially opens the gate 3 Closes at once No effect No effect STOP 1 Disables OPEN commands Stops pause time count Stops operation Stops operation PHOTOCELLS 2 No effect Stops operation and...

Page 15: ......

Page 16: ...ungen in vorliegendem Handbuch sind unverbindlich FAAC behält sich das Recht vor ohne die wesentlichen Eigenschaften dieses Gerätes zu verändern und ohne Verbindlichkeiten in Bezug auf die Neufassung der vorliegenden Anleitungen technisch bzw konstruktiv kommerziell bedingte Verbesserungen vorzu nehmen Las descripciones y las ilustraciones de este manual no comportan compromiso alguno FAAC se rese...