E145
6
732783 - Rev.C
ENGLISH
Translation of the original instructions
Display
Basic Function
Default
St
STATUS OF THE AUTOMATED SYSTEM:
1. set the selection:
Y
to SAVE and EXIT programming
no
to EXIT programming WITHOUT SAVING
2. press
F
to confirm; when completed, the
status of the automated system
will
appear on the display once again:
Y
00
= CLOSED
01
= OPEN
02
= Stationary and then “OPENS”
03
= Stationary and then “CLOSES”
04
= In “PAUSE”
05
= Opening
06
= Closing
07
= FAIL SAFE in progress
08
= Verifying
BUS-2EASY
devices
09
= Pre-flashes and then “OPENS”
10
= Pre-flashes and then “CLOSES”
11
=
Emergency open
12
=
Emergency close
HP
=
Hold position
3.2 ADVANCED PROGRAMMING
Display
Advanced Function
Default
bo
TIME OF MAXIMUM POWER AT START-UP
01
cS
FINAL STROKE WHEN CLOSING (FLUID HAMMER)
(NOT displayed with
the
FC
=
1
function)
no
rS
REVERSE STROKE WHEN OPENING
(
NOT displayed with the
FA
=
1
function)
no
Od
LEAF OPENING DELAY (only displayed with the
Mn
=
2
function)
02
r1
LEAF 1 DECELERATION
:
The deceleration space can be adjusted as a percentage of the total travel
of leaf 1.
Adjustable from
00
to
99
%, in 1% steps.
00
= no deceleration
01
= minimum deceleration space
99
= maximum deceleration space
20
r2
LEAF 2 DECELERATION (only displayed with the
Mn
=
2
function):
The deceleration space can be adjusted as a percentage of the total travel
of leaf 2.
Adjustable from
00
to
99
%, in 1% steps.
00
= no deceleration
01
= minimum deceleration space
99
= maximum deceleration space
20
PF
PRE-FLASHING
no
Ph
CLOSING PHOTOCELLS
no