11
ENGLISH
ENGLISH
Equipment lay-out for managing vehicles on exit lane
3.1 SAFETY INSTRUCTIONS
•
Before attempting any action on the system, cut out the
electrical power supply.
•
Install an omnipolar switch upstream of the power supply
line for the device, with contact opening distance of 3 mm. or
more. We advise you to use a 6A thermal breaker with omnipo-
lar switching.
3. ELECTRICAL PREPARATIONS
•
Make sure that a differential switch with a threshold of 0.03A
is installed upstream of the system.
•
Make sure that the earthing system is expertly made and
connect to it the metal parts of the closing element.
•
Apply all the instructions described in the preceding points to
all the lane devices, in addition to the Ticket Reader.
Fig.
12
Foundation plate for ParkLite column
Foundation plate for
620 rapid barrier (RH version)
Driving direction
Presence loop
Transit loop
2.7 POSITION OF EQUIPMENT
To ensure the parking system operates correctly, all the equip-
ment of the exit lane must be positioned, strictly observing the
dimensions shown in the lay-out below: