Table 2-1. Internal resistance, short circuit current (20

°

C)

±

10% Terminal type 

Battery Type 

Internal resistance (mΩ)± 10% 

Short circuit current (A)±10% 

Terminal Type 

FLL 12-17 

15,3 

350 

M5 

FLL 12-24 

10,2 

530 

M5 

FLL 12-31 

15,0 

800 

M6 

FLL 12-42 

12,0 

1050 

M6 

FLL 12-60 

10,0 

1260 

M6 

FLL 12-70 

7,5 

1720 

M6 

FLL 12-100 

5,0 

2150 

M8 

FLL 12-120 

4,7 

2380 

M8 

FLL 12-150 

3,8 

3200 

M8 

FLL 12-200 

3,4 

3500 

M8 

FLL 6-100 

2,1 

2600 

M8 

FLL 6-150 

3,2 

3100 

M8 

FLL 6-180 

3,1 

3800 

M8 

FLL 6-200 

4,4 

4100 

M8 

FLL 6-225 

4,1 

4300 

M8 

Note:  Short  circuit  current  will  decrease  the  voltage  of  the  battery  to  0V,  and  damage  the 

internal components of the battery. 

     

 

 

 

 

 

Summary of Contents for FLL 6V Series

Page 1: ...VE REGULATED LEAD ACID BATTERY FLL 6V 12V SERIES OPERATION MANUAL FAAM SpA via Monti zona industriale 63026 Monterubbiano AP Tel 39 0734 2581 Fax 39 0734 59729 Internet www faam com E mail info faam c...

Page 2: ...to overcharge battery shortly and short circuit shall be avoided Please do not attempt to dismantle the battery if some abnormal phenomena happen You should contact us immediately and our technicians...

Page 3: ...lection 8 12V Ampere Monoblock at 20 C 1 65V Cell 8 12V Ampere Monoblock at 20 C 1 70V Cell 9 12V Ampere Monoblock at 20 C 1 80V Cell 10 4 Installation 11 5 Operation 12 6 Storage 15 The quality certi...

Page 4: ...lid The technology conquers epoxy s weaknesses of aging and brickle And the amalgamation of the same ABS material ensures no leakage of solution Explosive proof valve with an acid filtering structure...

Page 5: ...2 Fig 1 1 Battery image Indication of Type F L L 20 or 10hr Rated Capacity LIFE LONG FAAM 6 or 12V...

Page 6: ...55 60 138 60 110 49 306 168 222 229 28 FLL 6 200 6 200 172 90 153 99 122 77 323 178 224 231 30 5 FLL 6 225 6 225 194 50 173 22 138 11 260 180 247 254 31 II Technical Characteristics Capacity and Influ...

Page 7: ...rent discharge rates From the figure we can see that when we adopt same type battery to discharge if the discharge rate is higher and the discharge current is larger then the discharge time is shorter...

Page 8: ...formula Ce CT 1 K T 20 T the ambient temperature K temperature modulus 10hr rate capacity test K 0 006 C 3hr rate capacity test K 0 008 C 1hr rate capacity test K 0 01 C Fig 2 2 Available Capacity VS...

Page 9: ...ng voltage is higher then the floating current is also higher it will accelerate the corruption the grid and shorten the life of the battery If the floating voltage is lower the battery can t be kept...

Page 10: ...1 15 0 800 M6 FLL 12 42 12 0 1050 M6 FLL 12 60 10 0 1260 M6 FLL 12 70 7 5 1720 M6 FLL 12 100 5 0 2150 M8 FLL 12 120 4 7 2380 M8 FLL 12 150 3 8 3200 M8 FLL 12 200 3 4 3500 M8 FLL 6 100 2 1 2600 M8 FLL...

Page 11: ...2 6 53 4 50 3 89 FLL12 60 12 75 66 53 66 37 56 31 77 25 18 12 86 8 82 6 08 5 25 FLL12 70 12 98 36 69 76 48 82 41 31 32 73 16 72 11 47 7 91 6 83 FLL12 100 12 128 62 91 22 63 85 54 02 42 80 21 86 14 99...

Page 12: ...7 33 92 26 87 16 68 11 42 7 87 6 72 FLL12 100 12 116 88 90 28 61 94 44 35 35 14 21 81 14 93 10 30 8 79 FLL12 120 12 137 51 106 21 72 87 52 18 41 35 25 66 17 57 12 11 10 35 FLL12 150 12 185 64 143 39 9...

Page 13: ...00 33 12 26 25 16 50 11 24 7 75 6 50 FLL12 100 12 93 88 78 64 58 85 43 32 34 32 21 57 14 70 10 13 8 50 FLL12 120 12 110 45 92 52 69 23 50 96 40 38 25 38 17 29 11 92 10 00 FLL12 150 12 149 11 124 90 9...

Page 14: ...ng Use insulating instruments during installation Do not use large torque to connect batteries Installation of abnormal batteries is prohibited Batteries are of sealed structure in normal condition th...

Page 15: ...operation please adjust the charge voltage according to environmental temperature see Table 4 1 Table 4 1 Floating Voltage VS Ambient Temperature Environmental Temperature C Floating Voltage V 0 02V...

Page 16: ...lows The charge time is 18 24 hours the charge time can be shortened when the batteries weren t deep discharged e g the charge time of 20 DOD batteries can be shortened to 10hours On condition of cons...

Page 17: ...10 15 20 25 30 1 9 2 0 2 1 2 2 2 3 Charging Voltage Per Cell V Charging Time h 0 20 40 60 80 100 120 140 Charging Voltage Per Cell Charging Current Capacity Charged Charged 0 10 20 30 40 50 60 70 Cha...

Page 18: ...lectrolyte In order to avoid perpetual damage to the plate caused by self discharge the batteries should be supplemental charged if they have been stored for three months The equalized charge method s...

Page 19: ...tteries need to yearly maintenance or even three years maintenance should be processed If all methods are ineffective please contact us Yearly Maintenance Repeat quarter maintenance and inspection Che...