UK/IRL
16
<
<
<
<
Dimension Terminal
position
(kW input 7.5 kW expressed in net)
Balanced flue
room sealed
Natural Draught
A
Direct below an opening, airbrick, opening
windows, etc.
300 mm
B
Above an opening, airbrick, opening window, etc.
300
mm
C
Horizontally to an opening, airbrick, opening
window, etc.
300 mm
D
Below gutters, soil pipes or drain pipes
500
mm
E Below
eaves
500 mm
F
Below balconies or cat port roof
600
mm
G
From a vertical drain pipe or soil pipe
300
mm
H
Dfrom an internal or external corner
600
mm
I
Above ground roof or balcony level
300
mm
J
From a surface facing the terminal
600
mm
K
From a terminal facing a terminal
600
mm
L
From an opening in the carport (e.g. window) into
the dwelling
1200 mm
M
Vertically from a terminal on the same wall
1500
mm
N
Horizontally from a terminal on the same wall
300
mm
P
From a vertical structure on the roof
600
mm
Q
Above intersection with roof
500
mm
Flue terminal
Fig. 3
Tabel 6