background image

8

3.3  

Discharge and outlet requirements

• 

Always use the supplied discharge materials for the supply   

 

and discharge ducts. Only with use of these materials 

Faber

  

 

can guarantee proper performance.

• 

When installing against a flammable wall, a special wall    

 

termination must be applied.

 

You can order this from Glen Dimplex Benelux BV.

3.4  

Outlets

Check whether the outlet meets all local regulations with regards to 

obstruction and vents.

 

Please note:

 

For proper functioning, the outlet must at least be 0.5m away  

 

from:

• 

Corners of the building.

• 

Roof overhangs and balconies. 

• 

Eaves (with exception of the roof-ridge edge) (see chapter 12)

4 Preparation and installation 

 instructions

4.1  

Gas connection

The gas connection must comply with the applicable local 

standards.

We advise using a Ø 15mm gas connection directly from the gas 

meter to the appliance, with a shut-off valve in the proximity of the 

appliance, which must always be freely accessible.

Position the gas connection so that it is easily accessible at all 

times for service, and that the burner unit can be disassembled. 

4.2  

Electrical connection

If for the power supply an adapter is used, then a 230VAC/50Hz 

wall socket must be mounted near the fire.

4.2.1 

Smart-Home installation

You can connect the control unit to the receiver with an external 

source, such as a Domotica home automation system, using the 

5-wire pin connector. 

(part G60-ZCE/500 The total length of the cable may not exceed 8 

meters, Signal relay (gold-plated contacts) or opto-couples are 

recommended! Art. No.: 06022950).

4.3  

Preparing the fire

• 

Remove the fire and accessories from the packaging.

• 

Clear a space to safely store the glass, if required.

• 

If required, remove the glass and remove the packaged parts  

 

from the fire.

• 

Prepare the gas connection on the regulator.

4.4  

Positioning the fire

Take the installation requirements into account (see Chapter 3). 

• 

First, determine the desired height of the platform and then   

 

tape the template (horizontally) onto the wall at that height    

 

(see Dimensional drawing 14.3).

• 

The platform height marked on the template is 400mm.

 

Higher platform levels are possible as long as the ceiling    

 

height “

G

” (size drawing 14.3) is not exceeded.

 

Lower installation is possible as long as “

F

” is not exceeded.

 

You may cut the template in intervals of 50 mm.

• 

Mark and then drill all required holes.

• 

Install the wall mount on the wall (fig. 1.1).

• 

Hang the fire on the wall mount. 

 

Vertically level the fire using the spacer at the bottom back of  

 

the gas fire (fig. 1.2).

• 

The feet underneath the fire can be retracted so that they are  

 

out of sight. (fig. 1.3) To do this, loosen the bolt, slide the feet  

 

upwards and then tighten the bolt.

4.5  

Installing the flue gas discharge pipes

• 

When penetrating a wall the opening must be at least 5mm   

 

larger than the diameter of the discharge material.

• 

Horizontal sections should be installed with a slope towards  

 

the fire (3 degrees).

• 

Build the system from the fire up (fig. 1.4). The sliding spacer  

 

allows for easy installation.

Please note:

 

The slider must be fixed with a drill screw.

• 

The wall duct may be shortened.

4.6  

False chimney breast installation

Suspend the false chimney breast from the 4 protruding bolts of the 

wall mount. Then secure it using the top two mounting holes (fig. 

1.5).

4.6.1 

False chimney breast top installation

The top of the false chimney breast can be installed without any 

mounting materials. 

(See fig. 1.6).

4.6.2 

Finishing the false chimney breast

If possible, conduct a performance test of the fire before finalizing 

the false chimney breast.

Chapter 7 “checking the installation”.

4.7  

Platform installation

• 

Install the platform according to fig. 1.7a and 1.7b

4.8  

Mounting the decorative materials

• 

First, install the left and right decorative materials securing    

 

them with the adjustable magnetic snappers (fig. 1.8).

• 

Then, install the lower decorative frame.

Prevent

 damaging the platform (fig. 1.9).

I n s t a l l a t i o n   I n s t r u c t i o n s

Summary of Contents for Concept III-700

Page 1: ...Concept III 700 40011626 1551 Concept III 700 ENG ...

Page 2: ...2 I n s t a l l a t i o n I n s t r u c t i o n s 1 1 1 2 B B A A 1 3 1 4 ...

Page 3: ...3 I n s t a l l a t i o n I n s t r u c t i o n s 1 6 1 7b 1 5 1 7a ...

Page 4: ...4 I n s t a l l a t i o n I n s t r u c t i o n s 1 9 2 2 1 8 2 1 B A ...

Page 5: ...5 I n s t a l l a t i o n I n s t r u c t i o n s 3 2 3 1 3 4 3 3 ...

Page 6: ...6 I n s t a l l a t i o n I n s t r u c t i o n s 4 2 4 4 4 1 4 3 ...

Page 7: ...eclaration will become null and void as soon as the unit is in any way modified without written authorisation of Glen Dimplex Benelux 2 Safety instructions The unit must be installed and checked every year according to these instructions and the applicable national and local regulations Ensure that the data on the type label matches the local gas type and pressure The settings and the construction...

Page 8: ...see Chapter 3 First determine the desired height of the platform and then tape the template horizontally onto the wall at that height see Dimensional drawing 14 3 The platform height marked on the template is 400mm Higher platform levels are possible as long as the ceiling height G size drawing 14 3 is not exceeded Lower installation is possible as long as F is not exceeded You may cut the templat...

Page 9: ...hat the pilot flame is well above the main burner and not covered by chips or a wood block Check the ignition of the main burner on full and small setting ignition must be smooth and quiet 7 2 Checking for gas leaks Check with a gas leak finder or spray all connections and pipes for gas leakage 7 3 Checking the burner pressure and primary pressure Check that the burner pressure and primary pressur...

Page 10: ...ion The pilot light The combustion chamber The glass The ceramic logs for breakage The outlet Replace if necessary Chips Embers 9 2 Cleaning the glass Most deposits can be removed with a dry cloth Clean the glass with a ceramic hob cleaner Please note Avoid fingerprints on the glass These are no longer removable after they are burnt in Now carry out check up as described in Chapter 7 Checking afte...

Page 11: ...pressure at full mark mbar 12 25 5 31 5 Injector main burner mm ST 800 ST 280 ST 280 Reduced input restraint mm 2 1 1 3 1 3 Pilot flame SIT160 SIT160 SIT160 Code pilot flame injector Nr 36 Nr 23 Nr 23 Diameter outlet inlet mm 100 150 100 150 100 150 Gas controle valve GV60 GV60 GV60 Gas connection 3 8 3 8 3 8 Electrical connection V 230 230 230 Batteries receiver V 4x 1 5 AA 4x 1 5 AA 4x 1 5 AA Ba...

Page 12: ...osition outlet Distance mm D Under a gutter 500 E Under a roof edge 500 F Under a carport or balcony 500 G Vertical downpipe 300 H Inside and outside corners 500 J From wall surface to a wall outlet 1000 K Two gable outlets against over each other 1000 L Distance between two roof outlets 450 M Two roof outlets above each other on a pitched roof 1000 N Two gable outlets next to each other 1000 Shor...

Page 13: ...raps removed Cable is free from any metal parts 4x 1 5V AA Alkaline Thermocouple circuit is interrupted check 8 wire cable from receiver to the gas valve If the wire on the bottom of the gas valve is not broken or stuck and makes a ground contact Motor gas valve doesn t work Micro switch on gas valve doesn t work 3 short beep s 1 long beep Faulty solenoid gas valve Replace the gas valve Replace fa...

Page 14: ... is leaking Glass seal is leaking Flue parts aren t 100 connected check flue system Replace batteries in the receiver Check the distance from thermocouple to pilot flame Measure the mvolts over the thermocouple required min 4mvolts over black and ground contact Flame stays blue lift from the burner and fire switch of Check flue calculation horizontal length to long Correct flue restrictor Flue par...

Page 15: ...poor or loose contact Short circuit in wiring Install a ground cable from the gas valve to the appliance Optional Step burner function can be turned ON and OFF only with remote RESET the receiver Check the wiring from solenoid valve to receiver Faulty solenoid valve Faulty receiver Repaire the wiring Replace solenoid valve Replace receiver I n s t a l l a t i o n I n s t r u c t i o n s ...

Page 16: ...1 6 14 Dimensional drawings 14 1 Concept III 700 I n s t a l l a t i o n I n s t r u c t i o n s ...

Page 17: ...1 7 14 2 Position gass connection I n s t a l l a t i o n I n s t r u c t i o n s ...

Page 18: ...for wall mount B Hole for wall duct C Mounting hole for false chimney breast D Position of gas tap E Top platform F Minimum height platform floor G Minimum height breast ceiling H Ceiling I Floor I n s t a l l a t i o n I n s t r u c t i o n s ...

Page 19: ...1 9 I n s t a l l a t i o n I n s t r u c t i o n s ...

Page 20: ...www faber nl info faber nl Saturnus 8 NL 8448 CC Heerenveen Postbus 219 NL 8440 AE Heerenveen Dealerinfo ...

Reviews: