background image

9

5 Removing the glass

5.1  

Removing the glass from the front

• 

Remove the decorative frame (fig. 1.9)

• 

Place suction cups onto the glass and remove the sealing    

 

cord from the groove. (fig. 3.1).

• 

Slide the glass to the top so that the bottom is released from  

 

the slot. Now pull the glass out and gradually down. (fig. 3.2)

5.2  

Removing the glass from the side

It is not necessary to take out the glass from the side to place 

the wood set or for maintenance.

• 

First remove the front glass (see chapter 5).

• 

Remove the decorative materials (fig. 1.8)

• 

Remove the platform (fig. 1.7a en 1.7b)

• 

Place suction cups onto the glass and remove the sealing    

 

cord from the groove. (fig. 3.3) 

• 

Slide the glass to the top so that the bottom is released from  

 

the slot. Now carefully slide the glass outwards and  

 

 

downwards (fig. 3.4) 

Please note:

Replace the glass in reverse order.

Clean all fingerprints on the glass; otherwise they will burn in once 

the fire is used.

6 Placing the decoration material

It is not permitted to use other or to add more material in the 

combustion chamber.

Keep the pilot light always free of decoration material!

Do not place all decoration material at one time on the burner; the 

fabric parts can block it.

6.1  

Wood set 

• 

Place some of the chips on the burner and on the bottom.

• 

Place the wood set according to the instructions (see fig. 4.1  

 

through 4.4 of the included wood set chart) 

• 

Divide the rest of the chips on the burner and on the bottom.  

 

Prevent a thick layer on the burner; this adversely affects the  

 

fire image.

Start the fire as described in the user manual. Check if the flame 

distribution is good. Move the chips if necessary, until a good flame 

distribution is achieved.

7 Checking the installation

7.1  

Checking the pilot light and main burner. 

Ignite the fire as described in the user manual.

• 

Check the ignition of the pilot light.

Please note: 

• 

Ensure that the ignition cable is not tight but hangs loosely    

 

under the unit, this is necessary for proper ignition. Remove  

 

all tie-wraps. 

• 

Check that the pilot flame is well above the main burner and  

 

not covered by chips or a wood block.

• 

Check the ignition of the main burner on full and small  

 

 setting.

 

(ignition must be smooth and quiet).

7.2  

Checking for gas leaks

Check with a gas leak finder or spray all connections and pipes for 

gas leakage.

7.3  

Checking the burner pressure and primary  

 

  pressure 

Check that the burner pressure and primary pressure match the 

information listed in the manual, Chapter 11 Technical Data. 

Measuring the primary pressure:

• 

Close the shutoff valve.

• 

Turn measuring nipple 

B

 (see fig. 2.1) some turns open and  

 

connect a measuring hose to the gas regulator.

• 

Take this measurement at highest setting of the fire and when  

 

the fire is set to pilot light.

• 

Do not connect the unit if the pressure is too high.

Measuring the burner pressure:

Check the burner pressure only with proper primary pressure. 

• 

Turn measuring nipple 

A

 (see fig. 2.1) some turns open and  

 

connect a measuring hose to the gas regulator.

• 

The pressure must correspond to the value indicated in the   

 

technical specifications of this manual. In case of deviation   

 

contact the manufacturer.

Please note:

Close all pressure measuring nipples and check for gas leakage.

7.4  

Checking the flame image 

Let the fire burn for at least 20 minutes at highest setting and check 

the flame for:

1.  Flame distribution

2.  Colour of the flames

If one or both points are unacceptable, check the following:

• 

The wood set preparation and/or the amount of chips on the  

 burner.

• 

The pipe connections for leaks (in case of blue flames).

• 

The outlet. 

 

Wall penetration with right side up and in the right    

  position 

7.5  

Flue gas analyzer.

If you are in possession of a CO/CO2 flue gas analyzer, then it is 

possible to check the supply air and the combustion gases.

To this end, the front of the fire is provided with two measuring 

pipes between the build-in frame and glass cover (fig. 2.2) 

A=discharge, B=supply.

The ratio CO2 and CO must not be greater than 1:100.

Example:

CO2 is 4% and CO is 400ppm, measured at the highest point

If the ratio is greater than 1:100 or exhaust gases are measured in 

the supply air, then also check above points.

I n s t a l l a t i o n   I n s t r u c t i o n s

Summary of Contents for Concept III-700

Page 1: ...Concept III 700 40011626 1551 Concept III 700 ENG ...

Page 2: ...2 I n s t a l l a t i o n I n s t r u c t i o n s 1 1 1 2 B B A A 1 3 1 4 ...

Page 3: ...3 I n s t a l l a t i o n I n s t r u c t i o n s 1 6 1 7b 1 5 1 7a ...

Page 4: ...4 I n s t a l l a t i o n I n s t r u c t i o n s 1 9 2 2 1 8 2 1 B A ...

Page 5: ...5 I n s t a l l a t i o n I n s t r u c t i o n s 3 2 3 1 3 4 3 3 ...

Page 6: ...6 I n s t a l l a t i o n I n s t r u c t i o n s 4 2 4 4 4 1 4 3 ...

Page 7: ...eclaration will become null and void as soon as the unit is in any way modified without written authorisation of Glen Dimplex Benelux 2 Safety instructions The unit must be installed and checked every year according to these instructions and the applicable national and local regulations Ensure that the data on the type label matches the local gas type and pressure The settings and the construction...

Page 8: ...see Chapter 3 First determine the desired height of the platform and then tape the template horizontally onto the wall at that height see Dimensional drawing 14 3 The platform height marked on the template is 400mm Higher platform levels are possible as long as the ceiling height G size drawing 14 3 is not exceeded Lower installation is possible as long as F is not exceeded You may cut the templat...

Page 9: ...hat the pilot flame is well above the main burner and not covered by chips or a wood block Check the ignition of the main burner on full and small setting ignition must be smooth and quiet 7 2 Checking for gas leaks Check with a gas leak finder or spray all connections and pipes for gas leakage 7 3 Checking the burner pressure and primary pressure Check that the burner pressure and primary pressur...

Page 10: ...ion The pilot light The combustion chamber The glass The ceramic logs for breakage The outlet Replace if necessary Chips Embers 9 2 Cleaning the glass Most deposits can be removed with a dry cloth Clean the glass with a ceramic hob cleaner Please note Avoid fingerprints on the glass These are no longer removable after they are burnt in Now carry out check up as described in Chapter 7 Checking afte...

Page 11: ...pressure at full mark mbar 12 25 5 31 5 Injector main burner mm ST 800 ST 280 ST 280 Reduced input restraint mm 2 1 1 3 1 3 Pilot flame SIT160 SIT160 SIT160 Code pilot flame injector Nr 36 Nr 23 Nr 23 Diameter outlet inlet mm 100 150 100 150 100 150 Gas controle valve GV60 GV60 GV60 Gas connection 3 8 3 8 3 8 Electrical connection V 230 230 230 Batteries receiver V 4x 1 5 AA 4x 1 5 AA 4x 1 5 AA Ba...

Page 12: ...osition outlet Distance mm D Under a gutter 500 E Under a roof edge 500 F Under a carport or balcony 500 G Vertical downpipe 300 H Inside and outside corners 500 J From wall surface to a wall outlet 1000 K Two gable outlets against over each other 1000 L Distance between two roof outlets 450 M Two roof outlets above each other on a pitched roof 1000 N Two gable outlets next to each other 1000 Shor...

Page 13: ...raps removed Cable is free from any metal parts 4x 1 5V AA Alkaline Thermocouple circuit is interrupted check 8 wire cable from receiver to the gas valve If the wire on the bottom of the gas valve is not broken or stuck and makes a ground contact Motor gas valve doesn t work Micro switch on gas valve doesn t work 3 short beep s 1 long beep Faulty solenoid gas valve Replace the gas valve Replace fa...

Page 14: ... is leaking Glass seal is leaking Flue parts aren t 100 connected check flue system Replace batteries in the receiver Check the distance from thermocouple to pilot flame Measure the mvolts over the thermocouple required min 4mvolts over black and ground contact Flame stays blue lift from the burner and fire switch of Check flue calculation horizontal length to long Correct flue restrictor Flue par...

Page 15: ...poor or loose contact Short circuit in wiring Install a ground cable from the gas valve to the appliance Optional Step burner function can be turned ON and OFF only with remote RESET the receiver Check the wiring from solenoid valve to receiver Faulty solenoid valve Faulty receiver Repaire the wiring Replace solenoid valve Replace receiver I n s t a l l a t i o n I n s t r u c t i o n s ...

Page 16: ...1 6 14 Dimensional drawings 14 1 Concept III 700 I n s t a l l a t i o n I n s t r u c t i o n s ...

Page 17: ...1 7 14 2 Position gass connection I n s t a l l a t i o n I n s t r u c t i o n s ...

Page 18: ...for wall mount B Hole for wall duct C Mounting hole for false chimney breast D Position of gas tap E Top platform F Minimum height platform floor G Minimum height breast ceiling H Ceiling I Floor I n s t a l l a t i o n I n s t r u c t i o n s ...

Page 19: ...1 9 I n s t a l l a t i o n I n s t r u c t i o n s ...

Page 20: ...www faber nl info faber nl Saturnus 8 NL 8448 CC Heerenveen Postbus 219 NL 8440 AE Heerenveen Dealerinfo ...

Reviews: