background image

                                   

 

>

 

>

 

>

 

>

 26 

UK 

IRL 

 

Appendix H: Dimensions Duet L with floorplate 

 

  

Summary of Contents for Duet

Page 1: ...DUET Installation Guide IRL UK 40010731 0842 ...

Page 2: ...1 UK IRL General 1 1 1 2 1 3 1 4 1 5 30cm A ...

Page 3: ... 2 UK IRL Duet 2 1 2 2 2 3 2 4 2 5 ...

Page 4: ...3 UK IRL 3 1 3 2 3 3 3 4 3 5 ...

Page 5: ... 4 UK IRL 3 6 3 7 3 8 3 9 4 0 4 1 ...

Page 6: ...5 UK IRL 4 2 4 3 5 1 A ...

Page 7: ...nce 13 4 6 Constructing the chimney breast 13 4 7 Placing the side glas 14 4 8 Placing the bottom plate 14 4 9 Placing the pebbles 14 4 10 Placing the front glass 14 5 Commissioning functional checks 15 6 Handing over final check and customer briefing 17 7 Servicing 17 Appendix A Example calculation 19 Appendix B Flue restrictor 20 Appendix C Installation of the flue 21 Appendix D Technical specif...

Page 8: ...he crate always check if the desired version has been delivered Special features Room sealed appliance inlet and outlet are led to the outside using a natural draught concentric pipe system 100 mm 150 mm no power fan required Air supply and flue gases go to outside atmosphere through wall or roof A horizontal extension is possible see appendix A and B Remote Control is standard This appliance come...

Page 9: ...ions as amended the relevant British Standards for Installation work Building Regulations Codes of Practice and the manufacturers instructions Always use an additional guard if there are elderly infirm or children in the same room of the appliance The installation should also be carried out in accordance with the following where relevant BS5871 Part1 BS5440 Parts 1 2 BS1251 Building Regulations Do...

Page 10: ...ace above the hearth by means of the grates supplied or a comparable alternative with a minimum air supply of 20000 mm Use special stucco min 100 C resistant or glass fibre wallpaper to prevent discoloration or tears etc Recommended drying time 1 day per mm finishing coat applied 3 2 Surround with cover plate If the cover plate which can be optionally ordered is used the chimney breast must be pla...

Page 11: ... regulations regarding disturbance good functioning and ventilation The terminal must be located so that the outlet is not obstructed If the flue terminal is located within 2 meters of a footway path or where people could come into contact with it then a suitable terminal guard must be fitted Terminals located close to shared walkways footpaths etc could be subject to legal constraints and this sh...

Page 12: ... as an air supply must only service this appliance A chimney that has previously been used for solid fuel must be swept before use The existing chimney needs to be airtight The existing chimney needs to have an opening of min 150 x 150 mm The chimney needs to be intact and well looked after Use the adjustable roof mounted terminal especially made for this and the chimney connection set For more in...

Page 13: ...bourhood of the hearth 4 3 Preparation of the appliance Remove the appliance from the crate and the pallet Make sure you don t damage the flexible gas pipes Remove the glass and take out the separately wrapped parts of the appliance see par 4 3 1 4 4 Removing the glass Clear out a safe place to put down the glass Remove the bottom sealing ledge see fig 3 2 and 3 3 Place the suction cups on the fro...

Page 14: ...and in the desired position on to the wall by means of the wedge bolts supplied see fig 1 4 Suspend the hearth from the wall brace and adjust it to a level height by means of the adjustable strut situated underneath the hearth Place the flue tube system see appendix C 4 6 Constructing the chimney breast Always place the ventilation grates supplied or a comparable alternative in the chimney breast ...

Page 15: ...d in fig 2 2 2 3 en 2 4 and make sure that the chips are not covered completely by the logs Spread the last chips around and between the logs Check if the pilot light is not covered by chips or a log Place the front glass now 4 9 Placing the pebbles Replace the bottom grate in the inner frame Fill the grate with the pebbles supplied see fig 2 5 Divide the pebbles evenly and avoid thick layers on t...

Page 16: ...ull output and low output ignition should be flawless and easy 5 1 2 Check the flue pipe system Let the hearth burn on full output Check the flame image There should be no flames against the glass and an even distribution of the flames If this is not correct check the positioning of the wood in the grate and the quantity of chips on the burner After 20 minutes check if the flames burn a clear yell...

Page 17: ...hearth is on full output and when it is only on the pilot light If the pressure is too low check if the diameter of the pipes is sufficiently large If the pressure is too high more than 5 mbar or higher you are not allowed to connect the appliance and you must get in touch with your energy supplier Measuring burner pressure Only perform this check if the initial pressure is correct Measuring the b...

Page 18: ...n off the gas supply before commencing any servicing Always test for gas soundness after refitting the appliance Routine anual servicing Clean if necessary a the pilot system b the burner c the combustion chamber d the glass Check the log layout and replace the embers if applicable Do the operating test as described in chapter 6 Check the flue system and terminal for damage and soundness visual in...

Page 19: ... are burnt in Place the glass in front of the appliance and fix the glass frame or use the glass clamps Cleaning the combustion chamber and burner If the burner is visibly damaged this can affect the distribution of the flame if so then replace the burner Remove the front glass and log holder if applicable Break the gas supply at the control valve Unscrew the burner assembly and take them out of t...

Page 20: ... A 1 m Roof mounted terminal 1 m Total effective height 2 m Always check if the calculated situation is allowed see appendix B Flue restrictor Calculation 2 Calculation horizontal extension fig 2b Flue length J L 0 5 0 5 1 m Elbows K M 2m 2m 4 m Terminal 1 m Total horizontal extension 6 m Calculation effective height Hvert Flue length H 1 m Always check if the calculated situation is allowed see a...

Page 21: ...d when the values are outside the table the combination is not allowed Normally the 30 mm flue restrictor is pre installed Horizontal length m Duet 0 1 2 3 4 5 6 0 x x x x x x x 0 5 x x x x x x x 1 0 0 0 x x x x 1 5 0 0 0 0 0 x x 2 30 0 0 0 0 0 0 3 30 30 0 0 0 0 0 4 40 30 30 0 0 0 0 5 40 40 30 30 0 0 0 6 50 40 40 30 30 0 0 7 50 50 40 40 30 30 x 8 50 50 50 40 40 x x 9 65 50 50 50 x x x 10 65 65 50 ...

Page 22: ...p every 2m so the weight of the pipes is not resting onto the appliance The outside of the pipe can become hot 140 degrees Stay 50 mm away from wall surface or sealing Make sure to provide sufficiently heat resistant isolation when going through the wall or roof Because of expansion or cooling down the concentric pipes can turn loose It is recommended to fix the spring clip with a self tapping scr...

Page 23: ...Efficiency class 2 2 Inlet pressure mbar 20 37 Gas rate l h 1016 347 Gas rate gram h 650 Working pressure high mbar 12 0 31 5 Injector size mm ST 800 ST 280 Reduced input restraint mm 2 10 1 30 Pilot assembly SIT 160 SIT 160 Code Nr 36 Nr 23 Flue system Flue size mm 100 150 100 150 Std Flue restrictor mm 30 30 Gas control GV 60 C4E3M6M C5D3M6M Gas connection Nut olive 8 mm 8 mm at 15ºC and 1013 mb...

Page 24: ...23 UK IRL Appendix E Dimensions Duet R ...

Page 25: ... 24 UK IRL Appendix F Dimension Duet L ...

Page 26: ...25 UK IRL Appendix G Dimensions Duet R with floorplate ...

Page 27: ... 26 UK IRL Appendix H Dimensions Duet L with floorplate ...

Page 28: ...27 UK IRL Appendix J Dimensions Convection grid ...

Page 29: ... 28 UK IRL Appendix K Dimensions Service hatch ...

Page 30: ...29 UK IRL ...

Page 31: ... 30 UK IRL ...

Page 32: ...www faber nl info faber nl Saturnus 8 NL 8448 CC Heerenveen Postbus 219 NL 8440 AE Heerenveen T 31 0 513 656500 F 31 0 513 656501 ...

Reviews: