background image

I n s t a l l a t i o n   I n s t r u c t i o n s

I n s t a l l a t i o n   I n s t r u c t i o n s

1 6

5.2  

Removing the glass from the side

It is not necessary to take out the glass from the side to place the 

log set or for maintenance.

MatriX 800-II en -III:

• 

First, remove the front glass (see Chapter 5.1).

• 

Remove the left or right clamp strip on the top (fig. 3.4).

• 

Place the suction cups on the glass (fig. 3.5).

• 

 See fig. 3.5, number:

 

1.  Slide the glass towards to you and to the top so the    

 

 

bottom and back side will release.

 

2.  Now, carefully get the underside towards to you and    

 

 

put the glass on a safe place.

Please note:

Replace the glass in reverse order.

Clean all fingerprints on the glass; otherwise they will burn in once 

the fire is used.

 

6 Placing the decoration material

It is not permitted to use other or to add more material in the 

combustion chamber.

Keep the pilot light always free of decoration material!

See fig. 4.0 to 4.5 or the included log set card:

• 

Divide the glass granulate on the perforated bottom plate.

• 

Place the 2 large wood blocks and make sure there is no    

 

glass granulate underneath.

• 

Place the other wood blocks.

• 

Divide the chips on the glass granulate and the perforated    

 

bottom plate.

• 

Start the fire as described in the user manual.

• 

Assess whether the flame distribution and the Symbio-effect  

 

is good. Move or remove any chips/glass granulate to a good  

 Symbio-effect.

• 

Replace the glass (Chapter 5) and check the fire image.

 

7 Checking the installation

7.1  

Checking the main burner ignition, pilot flame    

 

 

Ignite the fire as described in the user manual.

• 

Check that the pilot flame is well above the main burner and  

 

not covered by chips. 

• 

Check the ignition of the main burner on full and small  

 

 

setting. (Ignition must be smooth and quiet).

7.2  

Checking for gas leaks

Check with a gas leak finder or spray all connections and pipes for 

gas leakage.

7.3  

Checking the burner pressure and primary  

 

  pressure

Check that the burner pressure and primary pressure match with 

the information listed in the manual, Chapter 14 “Technical 

specifications”. 

Measuring the primary pressure:

• 

Close the shut-off valve.

• 

Turn measuring nipple B (see fig. 1.7) some turns open and  

 

connect a measuring hose to the gas regulator.

• 

Take this measurement at highest setting of the fire and when  

 

the fire is set to pilot light.

• 

Do not connect the unit if the pressure is too high.

Measuring the burner pressure:

Check the burner pressure only with proper primary pressure. 

• 

Turn measuring nipple A (see fig. 1.7) some turns open and   

 

connect a measuring hose to the gas regulator.

• 

The pressure must correspond to the value indicated in the 

technical specifications of this manual. In case of deviation contact 

the manufacturer.

Please note:

Close all pressure measuring nipples and check for gas leakage.

7.4  

Checking the flame image

Let the fire burn for at least 20 minutes at highest setting and check 

the flame for:

Flame distribution

Color of the flames

If one or both points are not acceptable then check:

• 

The log set layout and/or the amount of glass granulate/chips  

 

on the bottom plate.

• 

The pipe connections for leaks (in case of blue flames).

• 

Whether the correct flue restrictor is fitted. (see fig, 2.0 F, first  

 

remove hatch “G”).

• 

The outlet. 

 

Wall terminal right side up

 

Roof terminal on the right position

 

If the maximum horizontal flue lengths is not exceeded.

7.5  

Flue gas analyzer

If you are in possession of a CO/CO2 flue gas analyzer, then it is 

possible to check the supply air and the combustion gases.

There are two measuring pipes at the front of the fire between the 

mounting frame and the glass (fig. 2.1).

The ratio CO2 and CO must not be greater than 1:100.

Example:

CO2 is 4% and CO is 400ppm, measured at the highest point.

If the ratio is greater than 1:100 or exhaust gases are measured in 

the supply air, then also check above points.

 

Summary of Contents for MatriX 800 Series

Page 1: ...MatriX 800 serie 40011633 1714 MatriX 800 ENG ...

Page 2: ...I n s t a l l a t i o n I n s t r u c t i o n s 2 1 0 1 2 1 1 1 3 ...

Page 3: ...I n s t a l l a t i o n I n s t r u c t i o n s 3 1 4 1 5 1 6 1 7 D E 1 8 ...

Page 4: ...I n s t a l l a t i o n I n s t r u c t i o n s 4 2 0 F G 1 9 2 1 ...

Page 5: ...I n s t a l l a t i o n I n s t r u c t i o n s 5 2 2 2 3 2 4 H H I I ...

Page 6: ...I n s t a l l a t i o n I n s t r u c t i o n s 6 J L K H H 2 7 2 5 2 6 ...

Page 7: ...I n s t a l l a t i o n I n s t r u c t i o n s 7 2 9 2 8 ...

Page 8: ...I n s t a l l a t i o n I n s t r u c t i o n s 8 B B A C 3 0 3 1 1 2 3 3 1 C 2 3 4 3 3 2 3 3 ...

Page 9: ...I n s t a l l a t i o n I n s t r u c t i o n s 9 3 4 1 2 3 5 ...

Page 10: ...I n s t a l l a t i o n I n s t r u c t i o n s 1 0 4 1 4 2 4 0 ...

Page 11: ...I n s t a l l a t i o n I n s t r u c t i o n s 1 1 4 3 4 4 4 5 ...

Page 12: ...I n s t a l l a t i o n I n s t r u c t i o n s 1 2 4 6 ...

Page 13: ...rials and carpeted floors etc are attracted These parts can settle as soot on cold surfaces Therefore do not light the fire shortly after installation Light the fire for the first time and run for several hours on the highest setting so that the paint can cure Provide adequate ventilation so that any fumes can disperse we recommend vacating the room during this process Please note 1 All transport ...

Page 14: ...himney must be in good condition no leakage well cleaned For more information about connections to existing chimneys ask the installation manual chimney connection set 4 Preparation and installation instructions 4 1 Gas connection The gas connection must comply with the applicable local standards We advise using a Ø 15mm gas connection directly from the gas meter to the appliance with a shut off v...

Page 15: ...stance profile fig 2 4 J upper side flange combustion chamber fig 2 5 K distance holder glass support fig 2 6 L distance holder glass support fig 2 6 Please note Ensure that the fire is not load bearing with regard to the false chimney breast 4 6 3 Method I with cover strip fig 2 2 Build the false chimney breast or plateau against the moldings H and distance profiles I see fig 2 4 and 2 7 Keep a m...

Page 16: ...nd pipes for gas leakage 7 3 Checking the burner pressure and primary pressure Check that the burner pressure and primary pressure match with the information listed in the manual Chapter 14 Technical specifications Measuring the primary pressure Close the shut off valve Turn measuring nipple B see fig 1 7 some turns open and connect a measuring hose to the gas regulator Take this measurement at hi...

Page 17: ...e table we work with start length STL total vertical height TVH and total horizontal length THL Start length STL This is the first part that is placed on the fire and represents a certain value fig 12 1 12 2 and 12 3 A N and F This value is in the top row of the table see restrictor table 11 1 and 11 2 Total vertical height TVH TVH is the difference in height measured from the top of the unit to t...

Page 18: ...0 2 x x x x x x x x 11 60 2 30 2 0 2 x x x x x x x x 12 60 2 30 2 0 2 x x x x x x x x 13 70 2 30 2 0 2 x x x x x x x x 14 70 2 30 2 30 2 0 2 x x x x x x x 15 70 2 30 2 30 2 0 2 x x x x x x x 16 70 2 30 2 30 2 0 2 x x x x x x x 17 80 2 30 2 30 2 0 2 x x x x x x x 18 80 2 40 2 30 2 30 2 x x x x x x x 19 80 2 40 2 30 2 30 2 x x x x x x x 20 80 2 40 2 40 2 30 2 x x x x x x x 21 80 2 50 2 40 2 30 2 x x...

Page 19: ... 40 4 x x 10 50 4 50 3 50 4 50 4 50 4 45 4 45 4 x x 11 60 4 60 3 60 4 50 4 50 4 50 4 45 4 x x 12 60 4 60 3 60 4 60 4 50 4 50 4 50 4 x x 13 60 4 60 3 60 4 60 4 60 4 50 4 50 4 x x 14 70 4 70 3 60 4 60 4 60 4 60 4 50 4 x x 15 70 4 70 3 70 4 60 4 60 4 60 4 60 4 x x 16 70 4 70 3 70 4 70 4 60 4 60 4 60 4 x x 17 80 4 70 3 70 4 70 4 70 4 60 4 60 4 x x 18 80 4 80 3 70 4 70 4 70 4 70 4 60 4 x x 19 85 4 80 3...

Page 20: ...40 4 x x 10 50 4 50 3 50 4 50 4 50 4 45 4 45 4 x x 11 60 4 60 3 60 4 50 4 50 4 50 4 45 4 x x 12 60 4 60 3 60 4 60 4 50 4 50 4 50 4 x x 13 60 4 60 3 60 4 60 4 60 4 50 4 50 4 x x 14 70 4 70 3 60 4 60 4 60 4 60 4 50 4 x x 15 70 4 70 3 70 4 60 4 60 4 60 4 60 4 x x 16 70 4 70 3 70 4 70 4 60 4 60 4 60 4 x x 17 80 4 70 3 70 4 70 4 70 4 60 4 60 4 x x 18 80 4 80 3 70 4 70 4 70 4 70 4 60 4 x x 19 85 4 80 3 ...

Page 21: ...4 60 4 60 4 60 4 60 4 60 4 x x x x 11 70 4 70 4 70 4 60 4 60 4 60 4 60 4 x x x x 12 70 4 70 4 70 4 70 4 60 4 60 4 60 4 x x x x 13 70 4 70 4 70 4 70 4 70 4 60 4 60 4 x x x x 14 70 4 70 4 70 4 70 4 70 4 70 4 60 4 x x x x 15 70 4 70 4 70 4 70 4 70 4 70 4 70 4 x x x x 16 80 4 70 4 70 4 70 4 70 4 70 4 70 4 x x x x 17 80 4 80 4 70 4 70 4 70 4 70 4 70 4 x x x x 18 80 4 80 4 80 4 70 4 70 4 70 4 70 4 x x x...

Page 22: ...4 60 4 60 4 60 4 60 4 x x x x 11 70 4 70 4 70 4 60 4 60 4 60 4 60 4 x x x x 12 70 4 70 4 70 4 70 4 60 4 60 4 60 4 x x x x 13 70 4 70 4 70 4 70 4 70 4 60 4 60 4 x x x x 14 70 4 70 4 70 4 70 4 70 4 70 4 60 4 x x x x 15 70 4 70 4 70 4 70 4 70 4 70 4 70 4 x x x x 16 80 4 70 4 70 4 70 4 70 4 70 4 70 4 x x x x 17 80 4 80 4 70 4 70 4 70 4 70 4 70 4 x x x x 18 80 4 80 4 80 4 70 4 70 4 70 4 70 4 x x x x 19...

Page 23: ...I n s t a l l a t i o n I n s t r u c t i o n s 12 Examples flue materials fig 12 1 fig 12 2 fig 12 3 2 3 ...

Page 24: ...ontal direction x 1 5 45 Bend in horizontal direction x 1 flue pipes at an angle in meters x 0 7 meter Value Starter length STL First part on top of the appliance Flue length from 0 1m till 0 45m Flue length from 0 5m till 0 90m Flue length from 1m till 1 4m Flue length from 1 5m till 2m Flue length 2m or more Bend 90 Bend 45 30 or 15 Roof terminal Wall terminal Calculation Total rounded value Tot...

Page 25: ...ter just before the terminal Wall terminal 130 200 0 4 Restrictor size Value for the comma Extra information Value behind the comma Search in the table at TVH and THL and enter the value that is found If the detected value is a number check whether the completed STL is higher or equal to the value in the table Is the STL value lower as specified in the table then the installation is not possible S...

Page 26: ...gr h 720 710 Burner pressure at full mark mbar 10 5 21 28 4 Injector main burner mm 4x 1 3 1x 1 6 1x 0 8 4x 0 9 1x 0 8 4x 0 9 Reduced input restraint mm adjustable adjustable adjustable Pilot flame SIT145 SIT145 SIT145 Code pilot flame injector Nr 36 Nr 23 Nr 23 Diameter outlet inlet mm 130 200 130 200 130 200 Gas controle valve GV60 GV60 GV60 Gas connection 3 8 3 8 3 8 Electrical connection V 230...

Page 27: ...013 mbar gr h 860 830 Burner pressure at full mark mbar 13 8 20 5 27 1 Injector main burner mm 4x 1 3 1x 1 6 5x 0 9 5x 0 9 Reduced input restraint mm 2 1 1 6 1 6 Pilot flame SIT145 SIT145 SIT145 Code pilot flame injector Nr 36 Nr 23 Nr 23 Diameter outlet inlet mm 130 200 130 200 130 200 Gas controle valve GV60 GV60 GV60 Gas connection 3 8 3 8 3 8 Electrical connection V 230 230 230 Batteries remot...

Page 28: ...lets against over each other 1000 L Distance between two roof outlets 450 M Two roof outlets above each other on a pitched roof 1000 N Two gable outlets next to each other 1000 Short roof terminal Only for existing Chimney connection Extension pipe over roof 15 Terminal position Please note These rules apply only for the proper functioning of the unit for ventilation and environmental protection y...

Page 29: ...d Cut of a small piece from the sparking plug Tie wraps removed Cable is free from any metal parts 4x 1 5V AA Alkaline Thermocouple circuit is interrupted check 8 wire cable from receiver to the gas valve If the wire on the bottom of the gas valve is not broken or stuck and makes a ground contact Motor gas valve doesn t work Micro switch on gas valve doesn t work 3 short beep s 1 long beep Faulty ...

Page 30: ...lot burner is leaking Gasket between burner unit is leaking Glass seal is leaking Flue parts aren t 100 connected check flue system Replace batteries in the receiver Check the distance from thermocouple to pilot flame Measure the mvolts over the thermocouple required min 4mvolts over black and ground contact Flame stays blue lift from the burner and fire switch of Check flue calculation horizontal...

Page 31: ...aulty parts RESET the receiver Gas vlave broken poor or loose contact Short circuit in wiring Install a ground cable from the gas valve to the appliance Optional Step burner function can be turned ON and OFF only with remote RESET the receiver Check the wiring from solenoid valve to receiver Faulty solenoid valve Faulty receiver Repaire the wiring Replace solenoid valve Replace receiver ...

Page 32: ...I n s t a l l a t i o n I n s t r u c t i o n s 3 2 17 Dimensional drawings 17 1 MatriX 800 500 I ...

Page 33: ...I n s t a l l a t i o n I n s t r u c t i o n s 3 3 17 2 MatriX 800 500 IIL ...

Page 34: ...I n s t a l l a t i o n I n s t r u c t i o n s 3 4 17 3 MatriX 800 500 IIR ...

Page 35: ...I n s t a l l a t i o n I n s t r u c t i o n s 3 5 17 4 MatriX 800 500 III ...

Page 36: ...I n s t a l l a t i o n I n s t r u c t i o n s 17 5 MatriX 800 650 I 3 6 ...

Page 37: ...I n s t a l l a t i o n I n s t r u c t i o n s 3 7 17 6 MatriX 800 650 IIL ...

Page 38: ...I n s t a l l a t i o n I n s t r u c t i o n s 17 7 MatriX 800 650 IIR 3 8 ...

Page 39: ...I n s t a l l a t i o n I n s t r u c t i o n s 3 9 17 8 MatriX 800 650 III ...

Page 40: ...I n s t a l l a t i o n I n s t r u c t i o n s 4 0 17 9 Wall bracket ...

Page 41: ...I n s t a l l a t i o n I n s t r u c t i o n s 4 1 17 10 Remote acces door ...

Page 42: ...I n s t a l l a t i o n I n s t r u c t i o n s 4 2 17 11 Ventilation grid ...

Page 43: ...I n s t a l l a t i o n I n s t r u c t i o n s 4 3 17 12 Adjustable feet ...

Page 44: ...I n s t a l l a t i o n I n s t r u c t i o n s 4 4 www faber nl info faber nl Saturnus 8 NL 8448 CC Heerenveen Postbus 219 NL 8440 AE Heerenveen Dealerinfo ...

Reviews: