Commissioning (functional checks)
6.1
Check pilot ignition
•
Push in and turn the control knob (A) anticlockwise to the setting (small flame).
You will hear a tick meaning there is ignition. Hold the knob in and wait for a few
seconds while the air is purged.
•
Bring the knob back in the start position and turn the knob several times to the
position. Check that the pilot has lit.
•
Continue to hold in the control knob for a further ten seconds to ensure that the
pilot flame is stable.
•
Release the knob. The pilot should remain alight.
6.2
Functional burner check
•
Turn knob (B) to max. clockwise.
•
Turn the knob (A) more anticlockwise to the position (large flame). Now it is
possible to light the main burner.
•
Turn knob B anticlockwise to max. The main burner should light.
•
Check the ignition of the main burner on low and high setting.
•
Turn knob B clockwise till
●
The main burner is off.
•
Turn the knob A to
λ
. The pilot should go out.
6.3
Spillage test
•
The appliance should first be tested with all doors and windows closed in the room
of the installation and with any fan in the room running. Then repeated with any
interconnecting doors open to any rooms, which have extract fans, or similar
equipment, which may adversely affect the spillage test.
•
Allow to warm up for 5 minutes and then using a smoke match with holder set 100%
inside the square tube on the top of the appliance between the trim and the glass
frame. The installation is satisfactory if most of the smoke is drawn into the tube.
Fig. 6.1