INSTALLATION
TESTING BURNER FOR LEAKS
WARNING: Never check for
gas leaks with open flame.
1. Generously apply a noncorrosive leak
detection fluid to all connections.
2. Light the burner with the shutoff valve, no
more than half open, and holding a match
slightly in front of the pan (see
Lighting
Instructions
, page 12).
3. Inspect all connections for bubbles,
raw gas odor, or flame from any area
other than the burner (leaks). If leaks are
detected, shut off the gas valve immedi
-
ately. Tighten, or reassemble the loose
connection(s) using pipe joint compound
until burner system is leak free.
4. When the burner is tested and leak free,
observe the individual tongues of flame
on the burner.
Note: Let the burner manifold cool first
before removing to unclog port blockages.
The burner design includes more ports
on the outside of the bar. Make sure that
all ports are clear and producing flame
evenly across the burner. If any ports
appear blocked, clear them by removing
the burner manifold and reaming the ports
with a modified paper clip or other suit
able tool.
5. When finished testing, turn the gas shutoff
valve OFF to extinguish all flames.