9
Before making any connections, study the enclosed electrical diagrams carefully (Pic. 11, Pic. 12, Pic. 13).
IMPORTANT
: The whole electrical system must be earthed (Pic. 13).
-
Power supply, electric motor and flashing light
connections are made with electric cables with a section of 1.5 mm
2
for a maximum
distance of 50 m. For distances of over 50 metres, we recommend using electric cables with a section of 2 mm
2
.
- For
limit switches, photocells, pushbuttons and accessories
use cables with a 1 mm
2
section (Pic. 11 - Drwg. 3499).
- The
pneumatic safety rib
attached to the gate is connected via cable, a cable winder is to be provided to take up the slack, or by
radio
link
, in series with the
limit switches
or with the
receiving photocell
, connection diagram Drwg. 3499.
- The ELPRO 10 PLUS three-phase electronic programmer is installed in its own panel, inside the Fibo 300 protection cover; it is prepared
for all programmed automatic and semiautomatic logic services, line relays and incorporated indication lights (Pic. 11 - Drwg. 3499).
ELECTRICAL CONNECTIONS TO ELPRO 10 PLUS PROGRAMMER
PIC. 13
1 - Magnetothermal differential
mains switch, 0.03A type
2 - Cruastro radio link receiver
3 - Rubber pneumatic rib
4 - Cruastro radio link transmitter
5 - Miri 4 flashing light
6 - Polo 44 receiving photocell
7 - Polo 44 projecting photocell
8 - Prit 19 keyswitch
9 - Birio A8 aerial
10 -Astro 43 external radio receiver
11 -Pulin 3 wall-mounted push
button panel
12 -Internal photocell Receiver
Polo 44 on post
13 -Gate stop required
14 -Radio transmitter Astro 43 Small
15 -Fibo 300
16 -Electric cable containment
17 -Internal photocell Projector
Polo 44 on post
PLUS
10
n
°
2x1,5
n
°
4x1
n
°
4x1,5
400V
50Hz
n
°
4x1
n
°
2x1
n
°
4x1
n
°
2x1
n
°
4x1
n
°
4x1
n
°
4x1
1
2
3
4
5
6
3
4
7
8
9
11
12
13
13
17
10
15
16
14
PIC. 12
Hold on switched (Deadman) control:
Pedestrian Opening:
Trimmer T3
-
+
OPERATING MODES
from 3 to 30s. It can be activated by
any pulse (eg. by remote control)
superior to 2s
3
DIP-SWITCH 3
ON= Automatic Closing
OFF= No Automatic. Semi-automatic
closing by pulse
Automatic / Semiautomatic:
Automatic Operation:
any pulse opens the gate, the gate stays
open as long as the Dwell time expires as set by T2 trimmer, then
it closes automatically, no pulsing is required.
Semi-automatic Operation:
any pulse opens the gate that stays
open. A second pulse to Close is required for the gate to close.
Open and Close operations are achieved "by holding a
switch on" (no relay self-holding in involved) therefore a
phisical attendance is required to keep the gate opening or
closing until either the button or key is released.
Remote Controlled Operations Excluded during
Dwell Time on Automatic Mode:
3
ON= Automatic Closing
OFF= Closing by Pulse
5
ON: Step by step. Stop in between
OFF: Standard Operations
With this setting it is not possible to operate the gate by remote control during the dwell time on automatic
mode. DIP-SWITCH 2=ON, 3=ON and 5=ON
DIP-SWITCH 6
6
ON= Deadman Control. Dip-switch 4=OFF
and Dip-switch 3=OFF
OFF= Standard Operations
DIP-SWITCH No.3=ON Automatic Closing
Time clock
installation:
3
ON= Automatic Closing
OFF= No Automatic. Semi-automatic
closing by pulse
4
3
COMMON
COMMON
OPEN
NO
-
+
Pedestrian Trimmer T3
set on to zero
2
ON: No reversing on opening
OFF: Travel reversing on any pulsing
Dwell Time
from 5 to 128s
T2
-
+
COMMON
OPEN
4
3
How it works: Set the clock to the required times. On the pre-set time the gate is automatically opened and
held open. Any further pulsing (even by remote control) is not accepted by the system until the time pre-
set by the clock has expired. On expiring and after the pre-set dwell time the gate is closed automatically.
T3 trimmer on to zero, Dip-Switch 3=ON.
External time clock
Summary of Contents for FIBO 300
Page 1: ...G B INSTALLATION MANUAL...