5

LIMIT SWITCH FITTING INSTRUCTIONS

Fix the limit switch striking plates as shown in the diagram: the 

distance between the roller tip of the limit switch spring and the

striking plate front surface line must be 15 mm.

This distance will allow the correct operation of the limit switch 

spring in both travelling directions (pic. 5). Should the limit switch 

roller go beyond the 15 mm distance, unscrew and remove the

roller, then cut the spring to measure.

 IMPORTANT: 

the gate must stop before hitting the

 

gate  post  or  special  gate  stops  to  prevent  any

 

damage to its structure.

JUNCTION BOX/PIT

WHERE ALL CABLES ARE 

PRE-TERMINATED

WIRING DIAGRAM AND ACCESSORIES

Before fitting Mec 200 make sure the installation is pre-set for all the safety and control accessories as required (Pic. 6).

The safety edges, mechanically wire-operated and resistive 8,2 kΩ, fixed on the gate's leaf may be connected by cable, by mean of 

the safety radio device Arpo 58 or with the photocells Orbita 57.

General layout: it is the installer’s responsibility to lay the connection pipes and tubes as properly and correctly required.

IMPORTANT:

 all the electrical equipment to be properly earthed.

English

MEC 200

Pic. 5

Pic. 6

!

!

15 mm

LIMIT SWITCH STRIKING

PLATE TO BE FIXED

TO THE GATE BY BOLTS

LIMIT SWITCH ROLLER

FA

DI

NI

1

2

9

8

3

11

4

5

17

6

7

10

12

13

13

14

15

16

230 V

n°2x1

n°2x1

n°4x1

n°4x1

cable R

G58

n°4x1,5

n°4x1,5

n°4x1

n°2x1

n°3x1

1 - Miri 4 Flashing lamp - code 4612L

2 - Fit 55 recess photocell transmitter - code 551L

3 - Arpo 58 receiver - code 5801L

4 - Elpro 37 controller - code 7087L

5 - 230 V - 50 Hz - 0,03 A magneto-thermal

      differential circuit breaker (not supplied with the equipment)

      (2,5 mm² cable section beyond 100 m)

6 - Mec 200 gate operator

7 - Gear rack code 204L

8 - Arpo 58 transmitter - code 5802L

9 - Mechanical cable-operated edge - code 2077L

10 - Chis 37 recess key-switch - code 371L

11 - Vix 53/2 R plug-in radio receiver - code 5311L

12 - Birio A8 aerial - code 4605L

13 - Fit 55 recess photocell receiver - code 551L

14 - 0,5 m post - code 555L

15 - Post fixing plate with cover - code 554L

16 - VIX 53/4 TR transmitter - code 5313GL

17 - Gate stop

        (compulsory, not supplied with the equipment)

2

14

15

17

electro-mechanical sliding gate operator

Summary of Contents for MEC 200

Page 1: ... 12445 Electro mechanical sliding gate operator Vertical and horizontal installation Gear movements and worm gear coupling in oil bath fully mounted on ball bearings MEC 200 GB Instructions manual pages 1 8 the gate opener ...

Page 2: ...on The installer must inform and instruct the end user about the proper use of the system by releasing him a technical dossier including layout and components of the installation risk analysis verification of safety accessories verification of impact forces and reporting of residual risks INFORMATION FOR END USERS The end user is required to read carefully and to receive information concerning onl...

Page 3: ... gate stops are fixed in the open and closed gate positions so that the gate does not over travel the permitted limit and go out of the upper guide make sure that a system be mounted to the gate to prevent it from falling over make sure that once at the end of the permitted travel the gate does not hit the gate posts or special gate stops to avoid damages to its structure FITTING MEC 200 ON TO THE...

Page 4: ...out friction pic 4 IMPORTANT before definitely fixing any component make sure that the rack can mesh the driving gear of Mec 200 so that the whole system gate included can be smoothly run by hand the full travel open and close without any friction Remove the 2 mm shims only after having fixed the rack An adequete clearance between rack and gear has thus been achieved pic 4 English Pic 3 Pic 4 MEC ...

Page 5: ...s the installer s responsibility to lay the connection pipes and tubes as properly and correctly required IMPORTANT all the electrical equipment to be properly earthed English MEC 200 Pic 5 Pic 6 15 mm LIMIT SWITCH STRIKING PLATE TO BE FIXED TO THE GATE BY BOLTS LIMIT SWITCH ROLLER FADINI 1 2 9 8 3 11 4 5 17 6 7 10 12 13 13 14 15 16 230 V n 2x1 n 2x1 n 4x1 n 4x1 cable RG58 n 4x1 5 n 4x1 5 n 4x1 n ...

Page 6: ...be adjusted to the gate weight Adjusting is by a screw which is located on one side of the operator A special spanner E17 is provided with the equipment for this purpose unscrew the locknut the more you tighten the screw clockwise the more you increase the operator torque by unscrewing it torque is decreased Once set it to meet the site requirements tighten the locknut hard pic 9 ELECTRIC MOTOR CO...

Page 7: ...el Dimensions per gate leaf Weight per gate leaf Installation date Quantity of models installed Maintainer Date NOTE WELL this document must record any ordinary and extraordinary services including installation maintenance repairs and replacements to be made only by using Fadini original spare parts This document for the data included in it must be made available to authorized inspectors officers an...

Page 8: ...e phase 40 Nm 1 200 kg 19 5 kg 19 kg Three phase 40 Nm 1 250 kg 18 5 kg 18 kg Single phase 80 Nm 1 32 10 m 1 25 C 80 C Oil Fadini Item 706L 1 800 kg 23 5 kg 23 kg IP 55 inside the cover mechanical Three phase 80 Nm 1 850 kg 21 5 kg 21 kg Three phase 110 Nm 2 000 kg 25 5 kg 25 kg Mec 200 vertical Mec 200 horizontal OVERALL DIMENSIONS FITTING ACCESSORIES FOR INSTALLING Zinc coated steel base plate 2...

Reviews: