background image

 

 

 

   

 

Page 4/11 

VISY-ICI 485 

 

1

 

Introduction 

The VISY-ICI 485 is a communications adapter to connect VISY-Input 8 and VISY-Out-

put 4 components to the VISY-Command. 
The connection is established by an RS-485 interface. The interface is galvanically isolated 

from the rest of the circuit, and therefore from the VI-… interface card, by optocouplers 

and a DC/DC converter. Galvanic isolation improves the reliability of the communication. 
For  a  convenient integration into VISY-Command, the printed circuit board (PCB) of the 

VISY-ICI 485 is mounted on a module carrier for subsequent installation on DIN rails. 

2

 

Installation 

2.1

 

Safety precautions 

The following safety precautions must be observed during installation of the VISY-ICI 485 

communications adapter: 

 

The VISY-ICI 485 is designed for operation only with the VI-…  interface card. 

 

Modifications to the VISY-ICI 485 are prohibited without the prior consent of the 

manufacturer. 

 

The installation and configuration of the VISY-ICI 485 communications adapter 
must be carried out only by expert, authorised personnel. Specialised knowledge 

must be obtained by regular training. 

 

Operators, installers and service technicians must comply with all applicable safety 
regulations. This also applies to any local safety regulations and accident 

prevention regulations not stated in this technical documentation. 

The safety instructions in this manual are labelled as follows: 

 

If you do not observe these safety instructions, the risk of an accident 

exists or the VISY-X system could be damaged. 

 

Useful information in these instructions,  that should be observed,  is 

printed in italics and marked with this symbol. 

Summary of Contents for VISY-ICI 485

Page 1: ...2016 09 Revision 1 Article No 207150 FAFNIR GmbH Schnackenburgallee 149 c 22525 Hamburg Germany Tel 49 40 398207 0 Fax 49 40 390 6339 VISY ICI 485 Communications adapter for connecting VISY Input 8 an...

Page 2: ...Page 2 11 VISY ICI 485...

Page 3: ...7 2 6 Power supply LED 8 2 7 Communication LEDs 8 3 Configuration 9 3 1 RS 485 network bias and termination 9 3 2 Reference to more detailed instructions 9 4 Technical data 10 5 List of figures 10 6 L...

Page 4: ...CI 485 communications adapter The VISY ICI 485 is designed for operation only with the VI interface card Modifications to the VISY ICI 485 are prohibited without the prior consent of the manufacturer...

Page 5: ...Then press the other side of the module carrier onto the rail until this side snaps into place and the module carrier is firmly locked Figure 1 Assembly The VISY ICI 485 can be used only in conjunctio...

Page 6: ...ged as follows Figure 2 Connections LEDs and DIP switch 2 4 Connection to the VI interface card Connect the VISY ICI 485 to the VI interface card using the 6 pole ribbon cable supplied see Fig 1 This...

Page 7: ...re cable including signal ground GND is recommended in order to improve immunity to interference Figure 3 Connecting VISY Input 8 VISY Output 4 If shielded lines are used the shield should be placed o...

Page 8: ...green Meaning on VISY ICI 485 supplied with power off VISY ICI 485 not supplied with power Table 1 Power supply LED 2 7 Communication LEDs The two communication LEDs light up red whenever data are be...

Page 9: ...FF OFF OFF with series termination 120 100 nF ON OFF OFF ON with termination resistance 120 OFF ON ON OFF with bias factory default ON ON ON OFF with series termination 120 100 nF and bias ON ON ON ON...

Page 10: ...or connecting VISY Input 8 VISY Output 4 Operation indicator green LED Communication indicator red LEDs one for transmit one for receive Housing module carrier for mounting on DIN rails Dimensions h 7...

Page 11: ......