VISY-ICI 485 

Page 9/11 

 

3

 

Configuration 

3.1

 

RS-485 network – bias and termination 

Using the DIP switches, it is possible to bias the communication lines with a defined rest 

potential and activate the terminating impedances. 
By default, a bias is applied to the RS-485 network in order to improve reliability of 

communication. 
Under normal circumstances, communication in the RS-485 network should be 

troublefree without the need for terminating impedance activation because the data rate 

is relatively low. 
The following table shows the possible functions depending on DIP switch configuration: 

DIP switch

 

 
Function 

1

 

2

 

3

 

OFF  OFF  OFF  OFF  no termination and no bias 
ON  OFF  OFF  OFF  with series termination 120 

 / 100 nF 

ON  OFF  OFF  ON  with termination resistance 120 

 

OFF

 

ON

 

ON

 

OFF

 

with bias (factory default)

 

ON  ON  ON  OFF  with series termination 120 

 / 100 nF and bias 

ON  ON  ON  ON  with termination resistance 120 

 and bias 

Table 3: DIP switch 

 

All switch positions not shown in the table are unauthorised and will 

result in communication faults. 

 

3.2

 

Reference to more detailed instructions 

As is customary for the VISY-X System, all VISY-Input 8 / VISY-Output 4 components to 

be connected need  to be configured using the VISY-Setup configuration software. You 

will find detailed information of the components and their configuration in the following 

instruction manuals: 

 

Technical Documentation VISY-Setup 4 (English)   – Art. No. 207158 

 

Technical Documentation VISY-Input 8 (English)  

– Art. No. 207166 

 

Technical Documentation VISY-Output 4 (English)   – Art. No. 207131 

 

Summary of Contents for VISY-ICI 485

Page 1: ...2016 09 Revision 1 Article No 207150 FAFNIR GmbH Schnackenburgallee 149 c 22525 Hamburg Germany Tel 49 40 398207 0 Fax 49 40 390 6339 VISY ICI 485 Communications adapter for connecting VISY Input 8 an...

Page 2: ...Page 2 11 VISY ICI 485...

Page 3: ...7 2 6 Power supply LED 8 2 7 Communication LEDs 8 3 Configuration 9 3 1 RS 485 network bias and termination 9 3 2 Reference to more detailed instructions 9 4 Technical data 10 5 List of figures 10 6 L...

Page 4: ...CI 485 communications adapter The VISY ICI 485 is designed for operation only with the VI interface card Modifications to the VISY ICI 485 are prohibited without the prior consent of the manufacturer...

Page 5: ...Then press the other side of the module carrier onto the rail until this side snaps into place and the module carrier is firmly locked Figure 1 Assembly The VISY ICI 485 can be used only in conjunctio...

Page 6: ...ged as follows Figure 2 Connections LEDs and DIP switch 2 4 Connection to the VI interface card Connect the VISY ICI 485 to the VI interface card using the 6 pole ribbon cable supplied see Fig 1 This...

Page 7: ...re cable including signal ground GND is recommended in order to improve immunity to interference Figure 3 Connecting VISY Input 8 VISY Output 4 If shielded lines are used the shield should be placed o...

Page 8: ...green Meaning on VISY ICI 485 supplied with power off VISY ICI 485 not supplied with power Table 1 Power supply LED 2 7 Communication LEDs The two communication LEDs light up red whenever data are be...

Page 9: ...FF OFF OFF with series termination 120 100 nF ON OFF OFF ON with termination resistance 120 OFF ON ON OFF with bias factory default ON ON ON OFF with series termination 120 100 nF and bias ON ON ON ON...

Page 10: ...or connecting VISY Input 8 VISY Output 4 Operation indicator green LED Communication indicator red LEDs one for transmit one for receive Housing module carrier for mounting on DIN rails Dimensions h 7...

Page 11: ......

Page 12: ...FAFNIR GmbH Schnackenburgallee 149 c 22525 Hamburg Germany Tel 49 40 39 82 07 0 Fax 49 40 390 63 39 E mail info fafnir com Web www fafnir com...

Reviews: