89
Trendline 3
this case the start time will be determined automatically.
Configuring automatic adjustment
Automatic adjustment of alarm values can be defined for each characteristic
value
(acceleration, demodulation, velocity, temperature and ISO 10816-1) of
the element selected in the configuration tree.
To activate the automatic adjustment for one characteristic value proceed as
follows:
Select the characteristic value.
Enter the
main alarm
adjustment as a factor of the average value.
Enter the
pre-alarm
adjustment as a percentage (less than 100).
or:
Click
Recommended
to set the values recommended by Trendline.
For the ISO 10816 value, the alarm limits can only b e created
within the class b oundaries of pre-alarm (C) and main alarm (D).
More information ab out ISO 10816 classes can b e found in the "
ISO 10816
" chapter.
The values suggested b y Trendline for the automatic adjustment
of alarm values are b ased on empirical values used b y FAG
Industrial Services Gmb H. Because entirely different settings
may b e required, depending on the properties of the
components b eing monitored, these must b e regarded purely as
suggested values, which are completely non-b inding. The user
is always responsib le for selecting appropriate alarm values.
Click
Execute
to apply the settings.
The Trendline software adapts the alarm limits of the selected elements. A green
check mark displays a successful adjustment at the measurement point. A red
struck out circle indicates that the adjustment failed. In this case check the
settings and repeat the configuration.
Click
Close
to exit the alarm limit adjustment.