18
Subject to change without notice.
Version5_20200424
1.
In this menu you can select precise % values in order to ensure that levels are equal in a luminaire zone.
2. Scene Exit can be considered a series of complex functions.
3.
The “Remain in Scene Until On/Auto” function will remain active for a full year, provided that you do not press On/
Auto on the touch panel, which reverts to normal operation, or use “Revert to Auto Mode” in the app, which also
disables the scene.
4. The “Absence” function exists in order to able to automatically revert to normal operation once presence detection no
longer applies, and the time delay has elapsed. The light adjusts to low level, then switches off – now in normal operation.
5. Exit times are used to automatically exit the scene value and revert to normal operation. This is not contingent on
presence.
6.
The “Manual On/Auto Off” function is also referred to solely as Manual On. It disables automatic switch-on when a
zone detects presence. The light must be switched on manually at the touch panel, or via the app. The light switches
off as normal after last presence and according to the time setting.
NOTE! This function can only be used on nodes run-
ning version 160 or later.
Configuring scenes cont.
Point the dongle at a sensor and press the “Enable” button.
If several luminaires are to have the same function, you can relay the set
-
ting.
This also applies to resetting the function.
NOTE! This function can only be used on nodes running version 160 or later.
2
4
5
3
1
6
Summary of Contents for e-Sense Organic G3
Page 1: ...e Sense Organic G3...