Remote modules. RIO5, RIOW and RIOR series.
CNCelite
8058 8060
8065 8070
4.
RIOW REMOTE MODULES.
(CANOPEN PROTOCOL).
RIOW-CANOPEN-STAND
mod
ule
. Lead
ing
(first) modu
le.
ꞏ64ꞏ
R
EF
. 2107
4.5.4
Meaning of the LED's.
While staring the module up, the LED's indicate the stage the node is in and its status.
When a module is in configuration mode (dipswitch value equal to ꞏ0ꞏ), the LED's indicate
the speed selected at the module. See
LED's STOP, RUN, TX overflow and RX overflow.
The top four LED's of the module (STOP, RUN, TX overflow and RX overflow) indicate the
status of the node and of the communication through the CAN bus.
Node status.
Meaning.
Initializing stage
After starting up or after a reset, the module goes into the initializing stage
to run an autotest. During the initializing stage, the I/O LED blinks orange
until it changes to red.
• If the module is properly initialized, it changes to the pre-operative
stage, the I/O LED changes to green and the RUN LED blinks.
• If the module detects any problem in the initializing stage, it changes
to the stop stage, the I/O LED blinks red and the STOP LED turns
on. The blinking rate of the I/O LED indicates the detected error.
Pre-operative stage.
In this stage, the module configures the bus.
During the pre-operative stage, the I/O LED turns green and the RUN
LED blinks.
Operative stage.
In this stage, the module is ready to work.
In the operative stage, the I/O and RUN LED's turn green.
Stop stage.
This stage indicates an error at the node.
The STOP LED turns on in the stop stage.
STOP
RUN
Meaning.
OFF
OFF
Module turned off or in initializing stage.
OFF
Blinking
slow
Module in pre-operative stage.
OFF
ON
Module in operative stage.
ON
OFF
Module in stop stage. Node configuration error or bus error.
OFF
Blinking
fast
Module in pre-operative stage. Module error.
Blinking
fast
Blinking
fast
Module in pre-operative stage. Module error.
Blinking
fast
OFF
Module in pre-operative stage. Module error.
TX overflow
RX overflow
Meaning.
OFF
OFF
Module turned off or in initializing stage.
- - -
ON
Data reception error.
ON
- - -
Data sending error.
Blinking
fast
Blinking
fast
Too many errors at the node.
Summary of Contents for CNC 8065elite T
Page 1: ...Ref 2107 8058 8060 8065 8070 CNCelite Remote modules RIO5 RIOW and RIOR series...
Page 6: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 6 REF 2107...
Page 12: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 12 REF 2107...
Page 14: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 14 REF 2107...
Page 18: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 18 REF 2107...
Page 20: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 20 REF 2107...
Page 22: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 22 REF 2107...
Page 24: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 24 REF 2107...
Page 125: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 125 User notes REF 2107...
Page 126: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 126 User notes REF 2107...
Page 127: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 127 User notes REF 2107...