Power supplies
2.
94
Ref.1912
DDS
HARDWARE
· 62 ·
Connection terminals for the power DC BUS
At the bottom of the module, covered by the screwed-on lid on the right
(see figure
and figure
) the power supply offers the
terminal for the power bus. This bus provides a dc voltage output of 565 V
DC (when the line voltage is 400 V AC) that feeds all the drives that are part
of the DDS system.
All the modules powered with the same power supply must be connected
through the power bus and this condition is a must to run it.
Two plates are supplied with each module to join them with the adjacent
drives.
FAGOR power supplies have a soft-start for charging the power bus.
The soft start begins when these two conditions, that are necessary and
sufficient, are met:
No errors at the modules connected through the internal bus (X1
connector).
Presence of the three mains phases at the input of the module.
This startup process begins when the FAULT indicator stops blinking and
ends when the status indicator DC BUS ON turns on.
WARNING.
Never connect the power DC BUS while the system is running.
There are voltages of about 600 V DC!
MANDATORY.
The tightening torque of these terminals must be between
2.3 and 2.8 N·m. This point is very important to ensure good electrical
contact between modules.
WARNING.
Before handling these leads, proceed in the following order:
Stop the motors.
Disconnect the line voltage at the electrical cabinet.
Wait, before handling these leads. The power supply module needs time
to decrease the voltage of the power bus down to safe values
(< 60 V DC). The green indicator DC BUS ON being turned OFF does
not mean that the power bus may be handled or manipulated.
The discharge time depends on the number of elements connected and
it is about 4 minutes.
WARNING.
The power DC BUS of different power supply modules must
never be connected in parallel.
MANDATORY.
If necessary, the auxiliary power supply APS-24 (24 V DC,
10 A) can only be connected to the DC BUS of any regenerative power
supply XPS when the version label of the APS-24 (located on top of it)
indicates a version newer than
PF 23A
.
WARNING.
Never install an APS-24 to the DC BUS of a DDS system with
a regenerative power supply XPS if the version of the APS-24 is PF 23A or
older.
Summary of Contents for DDS Series
Page 1: ...DRIVE DDS Hardware manual Ref 1912...
Page 6: ...6 Ref 1912 DDS HARDWARE 6 I This page intentionally left blank...
Page 9: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 16: ...Ref 1912 DDS HARDWARE 16...
Page 20: ...Ref 1912 DDS HARDWARE 20...
Page 179: ...3 Drives Ref 1912 179 DDS HARDWARE...
Page 180: ...3 Drives Ref 1912 DDS HARDWARE 180...
Page 200: ...4 AUXILIARY MODULES Auxiliary modules Ref 1912 DDS HARDWARE 200...
Page 260: ...7 Cables Ref 1912 DDS HARDWARE 260...
Page 397: ...Sales models 12 Ref 1912 397 DDS HARDWARE 12 9 Order example F H12 21 Order example...
Page 404: ...13 Compatibility Ref 1912 DDS HARDWARE 404...
Page 405: ......