background image

5

APPLIANCE SAFETY LOCK-OUT

This boiler has a cut-out indicator built in to it. Whenever a malfunction is detected in the ignition of the boil-
er, the boiler switches off automatically and the cut-out indicator lights up (red indicator light) To reset the boil-
er press the  restart switch. The red indicator light should go out. IMPORTANT: Whenever the boiler has been
left idle for any length of time, or when a new gas bottle is installed (propane models), the appliance may
switch off due to the presence of air in the pipes. In cases such as these, repeat the ignition operation until
all of the air has been vented from the system.

FROST PROTECTION

Providing the boiler power supply and gas supply is connected and the main control switch is in the summer
setting the boiler will automatically fire on minimum setting when near freezing conditions are detected. When
the temperature in the system reaches 30

°

C it will switch off.   For winter storage see notes at the end of this

section.

ANTI PUMP SEIZURE DEVICE

When central heating in not being used, but the boiler is in the summer setting (for domestic hot water only)
the pump will automatically run for three minutes every 24 hours to prevent it seizing. If the appliance has
been shut down with the gas and electrical supply switched off for a period, this device will not work. The
pump may be found to have jammed when the appliance is switched back on. If so, refer to “Routine
Servicing”page 19 .

PRESSURE GAUGE

The pressure gauge should indicate approximately 1 bar. If the pressure is seen to decrease over a period of
time there is a water leak. Consult your installer or service engineer.

ROUTINE SERVICING

To ensure continued safe and efficient operation of the appliance it is recommended that it is checked and
serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular instal-
lation conditions and usage but in general once a year should be regarded as a minimum even if only occa-
sional usage has occurred. It is the law that any service work MUST be carried out by a registered engineer
such as CORGI registered personnel.

SAFETY

It is essential that these instructions are strictly followed for the safe and economical operation of this appli-
ance. The appliance is a fan-assisted balanced flue gas boiler and therefore the flue terminal MUST NOT BE
OBSTRUCTED under any circumstances. If it is damaged, turn off the appliance and consult your installer,
or service engineer. If it is known or suspected that a fault exists on the appliance it MUST NOT be used until
the fault has been rectified by a competent person.

PRECAUTIONS AGAINST FREEZING DURING WINTER STORAGE

During cold periods and if the boiler is situated in a place exposed to frosts, the D.H.W. circuit must be drained
down as follows:

- Turn off the cold water Supply

- Open all the hot water outlet taps on the installation (at least one tap should
be found at a level lower than the heater).

- Release the drain plug (shown opposite) which can be seen from under the
boiler.

- When the operation is finished, close the hot water outlet taps and replace
the drain plug.

- To put the boiler back into service, open the cold water inlet tap.

NOTE: In a Caravan Holiday Home installation there may be a drain cock on
the cold inlet under the van which may be used  instead of the drain plug on the boiler.

NOTE: It is not necessary to drain the heating circuit if the heating circuit has been filled with anti-freeze.

Summary of Contents for FEB-20E UK ECOPLUS

Page 1: ...FEB 20E UK ECOPLUS USER INSTRUCTIONS AND TECHNICAL INSTRUCTIONS...

Page 2: ...STRUCTIONS 3 2 GENERAL SPECIFICATIONS 6 3 TECHNICAL DATA 9 4 GENERAL INSTALLATION REQUIREMENTS 10 5 INSTALLATION INSTRUCTIONS 14 6 COMMISSIONING INSTRUCTIONS 17 7 ROUTINE SERVING INSTRUCTIONS 19 8 WIR...

Page 3: ...ELIMINARY WARNINGS Check all of the gas pipe joints and make sure that gas reaches the boiler with the gas cock turned on Make sure that the central heating circuit is completely full and vented The p...

Page 4: ...of simple mixer showers it is wise to turn the temperature selector down on the boiler before using the shower If a tap or shower head is too restrictive due to a fault or blockage the flow rate will...

Page 5: ...engineer ROUTINE SERVICING To ensure continued safe and efficient operation of the appliance it is recommended that it is checked and serviced as necessary at regular intervals The frequency of servi...

Page 6: ...bustion air Modulating gas valve with double safety valves Circulation pump with manual anti seizure device and speed selector Central heating expansion vessel Differential air pressure switch only al...

Page 7: ...limit stat 6 Ionisation electrode 7 Main Burner 8 Circulation Pump 9 Flow switch 10 Pressure relief valve 11 Fan 12 Heat Exchanger 13 Combustion Chamber 14 Expansion Vessel 15 Ignition electrode 16 D...

Page 8: ...lectrode 5 Burner 6 Injector Manifold 7 D H W Thermistor 8 Burner pressure nipple 9 Gas valve 10 Inlet pressure nipple 11 Gas inlet 13 D H W outlet 14 Heating flow 16 Flow switch 17 Water filter 18 Co...

Page 9: ...6 D H W Nominal Flow l min 10 Minimum Flow Rate Required to Activate D H W Mode l min 2 Maximum C H 3 Maximum D H W 10 Operating Pressure bar Minimum D H W 0 25 Expansion Vessel Capacity l 7 Central...

Page 10: ...in any way as over riding statutory obligations 4 2 BOILER LOCATION In positioning the boiler the following limitations MUST be observed The position MUST allow for a suitable flue termination to be m...

Page 11: ...rt of the terminal is fitted less that 2M 78 in above ground above a balcony or above a flat roof to which people have access the terminal MUST be protected by a purpose designed guard In certain weat...

Page 12: ...should be 3A This connection should be readily accessible and be made adjacent to the boiler 4 6 GAS SUPPLY A Propane gas supply at 37m bar is required Ensure the regulator is of sufficient capacity...

Page 13: ...hin the prescribed limits refer to technical data page 7 If neces sary a pressure reducing valve should be fitted to the mains supply before D H W inlet connection The DHW performance is summarised in...

Page 14: ...about 6mm should be allowed on the flue pipe to stop water ingress A screw fixing should be made on the bottom rail of the boiler to secure it during transport Use the paper template to mark out the...

Page 15: ...closed Any 24V controls may be used but gold contacts are recommended DO NOT under any circumstances use a mains supply to the stat as you will blow the P C B in the boiler Only voltage free switching...

Page 16: ...the available length by 0 8m See installation examples It is recommendable to fit the pipe at a slight 2 or 3 downwards incline to prevent any water or condensa tion from entering in the boiler Where...

Page 17: ...boiler is fitted with an automatic air vent Check that the cap found on the top left surface of the boiler is loose In order to fill the installation correctly the following sequence must be followed...

Page 18: ...e boiler is ready to supply it giving priority to the D H W with the central heating on standby until the D H W demand ceases 6 5 4 Turning the boiler off Turn the main control switch to the O setting...

Page 19: ...ency of servicing will depend upon the particular installation con ditions and usage but in general once a year should be adequate It is the law that any service work must be carried out by registered...

Page 20: ...BURNER PRESSURE This is factory set but should you suspect a problem proceed as fol lows There are two nipples on the gas valve an inlet pressure nip ple situated at the lower end marked in and a bur...

Page 21: ...alve 2 10 Flow switch 11 Air pressure switch 12 Room thermostat optional 13 Terminal block Room thermostat 14 Clock connection 15 Modulating Electro valve 16 Ionisation electrode 17 High limit stat 19...

Page 22: ...equence of the red neon 5 seconds 1 sec 1 sec 1 sec 1 sec 1 sec 1 sec 5 seconds N B The sequence repeats until either the reset button is depressed or the fault rectified Some faults require the compo...

Page 23: ......

Reviews: