AC Brushless Servo Drive System Manual Ver: 0002
ACa - 15 / 32
Preliminary
Drive Overcurrent. There has been an instantaneous current peak greater than the maximum
allowed. Get in contact with Fagor Automation.
Drive Overvoltage. The internal Bus voltage has exceeded 430 Vdc.
Solutions: The Ballast circuit may be defective or the supply voltage is too high. The external
Ballast hasn`t been installed correctly, or its value is not right.
Ballast overload warning (fast blinking)
The Ballast i2t protection is activated. If it goes on, the error will be activated.
Ballast overload error.
After the previous warning, the Ballast i2t protection has gone off.
Solutions: Install an external Ballast resistance, and set the RAPT = 10 Ohms.
Internal fault. Internal control error, or the RIT value is wrong.
Phase droped. Any of the main phases has droped, or a mains microcut has been longer than
100 ms.
Note: All the alarms are latched, the unit (control and power supply) must be powered off and
turned back on after 30 seconds. Or push the Reset button.
2.5
SPECIFICATIONS PLATE AND SALES REFERENCE
Examples of the
specs plate that comes with
each Fagor ACS drive.
Codes of the sales
reference of Fagor ACS
drives.
"PC", "PP", "VAR" and "FR" indicate manufacturing related aspects (hardware design versions)
that are useful for technical consultations and repairs.
A.C.S. DRIVES
Example:
ACS - 05
A.C. SERVODRIVE
CURRENT
Rated
Peak (0.5 sec)
05
2,5 Amp
5 Amp
10
5 Amp
10 Amp
20
10 Amp
20 Amp
30
15 Amp
30 Amp
AC SERVODRIVE
Fagor Automation S. Coop.(Spain)
MODEL:
ACS-05
S.N.: 202-1904001
PC
00A
FR
VAR
00A
PP
00A
INPUT :
OUTPUT:
3 X 220 VAC / 50-60 Hz
0-200 VAC
Io
Imax
5
10
Amp
Amp
W: 3,85 Kg