www.Fagorcommercial.com
PAGE 16
REACH-INS OPERATIONAL SERVICE MANUAL / Rev.JUN. 2015
Setting type C parameters
Type C parameters include the type F parameters plus all the other control parameters.
Procedure:
1.
Press Prg/Mute one or more times to return to the standard display;
2.
Press Prg/Mute for more than 3 seconds (if an alarm is active, the Buzzer is muted): the
display will show the code PS (Password) and The number 0;
3.
Press UP/DOWN and enter the password: 22. Press Set, the display Shows parameter/2;
4.
Press UP or DOWN until reaching the desired parameter: when Scrolling, an icon is displayed
that represents the category the Parameter belongs to (see the table below and the
parameter table);
5.
Press the SET button to display the value of the parameter;
6.
Press UP/DOWN until reaching the desired value;
7.
Press Set to temporarily save the new value and display the parameter Code again;
8.
Repeat steps 4) to 7) to set other parameters;
9.
To permanently save the new values of the parameters, press Prg/Mute for 5 seconds. This
exits the parameter setting procedure.
Important:
•
If the controller is powered down before pressing Prg/mute, all the changes made to the
parameters will be lost;
•
In the two parameter setting procedures (F and C), the new values are only saved after having
pressed Prg/mute for 5 seconds. When setting the set point, the new value is saved after
confirming with Set.
IF YOU NEED MORE INFORMATION PLEASE CONTACT THE TECHNICAL SUPPORT
Summary of Contents for QF-1
Page 1: ...REFRIGERATORS AND FREEZERS Manual for installation use and maintenance...
Page 11: ...www Fagorcommercial com PAGE 11 REACH INS OPERATIONAL SERVICE MANUAL Rev JUN 2015...
Page 22: ...www Fagorcommercial com PAGE 22 REACH INS OPERATIONAL SERVICE MANUAL Rev JUN 2015 QF1 QVF 1...
Page 23: ...www Fagorcommercial com PAGE 23 REACH INS OPERATIONAL SERVICE MANUAL Rev JUN 2015 QR2 QVR 2...
Page 24: ...www Fagorcommercial com PAGE 24 REACH INS OPERATIONAL SERVICE MANUAL Rev JUN 2015 QR 1G QVR 1G...