GRILLA PELLET SMOKER GRILL
OPERATION MANUAL
7
Low Limit Error Mode
• When the message “ErL” flashes on the LED Screen,
the Grilla temperature was at or below 110° for 10
consecutive minutes.
• The Auger and Igniter turn off. The Fan runs for
3 minutes and is then turns off.
• Low Limit Error Mode is cleared by setting the Control
Dial to the “Off” position.
High Limit Error Mode
• When the message “ErH” flashes on the LED Screen,
the Grilla temperature is greater than 615°. The Auger,
Igniter, and Fan turn off.
• High Limit Error Mode is cleared by setting the Control
Dial to the “Off” position.
Cool Down Mode
• When the Control Dial is turned to the “Off” position,
the Grilla enters the Cool Down Mode.
1. The Combustion Fan stays on.
2. The Auger turns off.
3. The Igniter turns off.
4. A cool down timer is flashes in the LED Screen
displaying; “CXX”, where XX = current cool down
timer numbers. The timer starts at 3 minutes and
goes down from there each minute.
5. When the timer on the LED Screen hits 0 minutes,
the Combustion Fan and LED Screen turn off.
Ignition Mode
When the Control Dial is turned from the “Off” position to “Smoke” or any of the temperature settings, and AC power
is applied, the Control Panel enters the Ignition Mode.
1. The Combustion Fan turns on.
2. The Igniter turns on.
3. The fuel feed Auger turns steady on delivering fuel at its maximum rate.
4. The current temperature is shown in the LED Screen along with 3 flashing dots, signifying the Grilla is in Ignition
Mode and the Igniter is on.
5. At 4 minutes:
- If Control Dial is set to “Smoke”, the Auger runs per Smoke Switch setting.
- If the Grilla temperature has increased 30° or is over 150°, Igniter turns off and the Grilla enters Smoke/Cook
operation.
6. At 5 minutes (if reached), Igniter turns off and the Grilla enters Smoke/Cook.