2

11-24 VDC

Less than 4 watts

Current mode input range 0-24 mA

35 mA maximum without damage

Voltage mode input range 0-12 VDC

Voltage mode input clamped at 13 VDC

150 psig

No less than 5 psig

above maximum output

11 SCFM @ 150 psig

supply at midscale output

2.0 SCFM @

15 psig output pressure

Instrument Air per ISA

S7.0.01 Recommended

Range 0 –160ºF

+(0.5%+0.06%/ºF)

of span

The Model T79xx Series includes Model T7900 and
Model T7950 Electro-Pneumatic I/P, E/P transduc-
ers Control Output Pressure in proportion to an
analog input signal.

When you apply initial power to the units,  

 dis-

plays on the Main Menu.  If the keypad is inactive for
three minutes, the unit returns to 

.  If power is

disrupted, the unit returns to its last setting when
power is restored.

These devices use feed and bleed solenoid valve
control technology, digital feedback electronic con-
trol, and an internal electronic pressure sensor to
achieve high accuracy pressure control.  Flexible
configuration and PID tuning capability ensure that
these pressure controllers can meet the most de-
manding air pressure control applications.

SPECIFICATIONS

Model T7900

Model T7950

Electrical

Supply voltage  . . . . . . . . . . . . . . . . . . . . . .  11-24 VDC
Power consumption. . . . . . . . . . . . .  Less than 4 watts
Analog input . . . . .  Current mode input range 0-24 mA
                                  35 mA maximum without damage

                 Voltage mode input range 0-12 VDC

                        Voltage mode input clamped at 13 VDC

Pneumatic

Maximum Supply pressure:

  

. . . . . . . . . . . . 200 psig

Minimum Supply Pressure. .  . . . No less than 5 psig
                                                   above maximum output

Forward Flow Capacity

. . . . . . . . . .   Up to 100
      SCFM @  170 psig

Exhaust Flow Capacity . . . . . . . . . . . .  Up to 50 SCFM

Air Quality . . . . . . . . . . . . . . . . . . . . . .      Instrument Air

           per ISA S7.0.01 Recommended

Input signal / Impedance

:  . . .  4-20 mA / 246 ohms,

                                                   0-10 VDC / 500k ohms

GENERAL INFORMATION

Electrical

Supply voltage . . . . . . . . . . . . . . . . . . . . . . .
Power consumption . . . . . . . . . . . . . . .
Analog input . . . . .

Pneumatic

Maximum Supply Pressure .  . . . . . . . . . . . . .    .
Minimum Supply Pressure . . . . . . .

Forward Flow Capacity . . . . . . . .

Exhaust Flow Capacity . . . . . . . . . . . . . .

Air Quality . . . . . . . . . . . . . . . . . .

Environmental - T7900 AND T7950

Operating Temperature . . . . . . . . . . . .
Temperature Effect . . . . . . . . . . . .

Summary of Contents for T79 Series

Page 1: ...RO PNEUMATIC TRANSDUCERS Analog Output Operation and Maintenance Instructions Software Version 3 45 and 3 46 SPECIFICATIONS Figure 2 Model T7950 Keypad Figure 1 Model T7900 Keypad Figure 3 Model T79xx Series Transducer Keypad Functions ...

Page 2: ...an internal electronic pressure sensor to achieve high accuracy pressure control Flexible configuration and PID tuning capability ensure that these pressure controllers can meet the most de manding air pressure control applications SPECIFICATIONS Model T7900 Model T7950 Electrical Supply voltage 11 24 VDC Power consumption Less than 4 watts Analog input Current mode input range 0 24 mA 35 mA maxim...

Page 3: ...entered on the setpoint which the unit does not respond Control Value Displays control input value Option Value Displays the feedback option output value Control Value 1 Sets the 0 Control Input value Control Value 2 Sets the 100 Control Input value Option 1 Sets the value of the current or voltage proportional to P1 Option 2 Sets the value of the current or voltage proportional to P2 2 Records th...

Page 4: ...Figure 2 Model T7950 Menu System 4 ...

Page 5: ...o Remote The Model T7900 T7950 control input channel is configured to accept an analog control signal to control the setpoint The Control Value displays the cur rent or voltage signal value at the control input terminals under all configurations The relationship between the control input signal and the output pressure is determined by and settings in the Configuration menu Output Control Analog Ou...

Page 6: ...unctions as setpoint control to the Model T7900 7950 Control Input set to LOCAL chooses the Setpoint using the keypad to control the output pressure In this mode the Model T7900 7950 control functions disregard the analog input channel NOTE The Control Input and the Analog Output Connection have four setting combinations that confi gure the Model T7900 7950 operation See Table 5 Quick Setup Calibr...

Page 7: ...tively mA 0 00 30 00 4 00 and 20 00 The Option Value will vary between 4 mA and 20 mA proportinally following the pressure output between 0 and 30 psig To achieve a reverse acting relationship set 20 00 and 4 00 or set 30 and 0 Look Ahead Items and Configuring Menu Tuning Coefficients The Model T7900 T7950 ships from the factory with nomi nal PID values Tune the PID coeffecients and for optimum pe...

Page 8: ...Kit 19715 2 3 To replace the solenoid valves in the Model T7950 install Service Kit 19715 1 4 For the Model T7900 install Service Kit 19375 1 5 To replace solenoid valves in the Model T7900 order quantity 2 of Part Number 290 IPI 001 2 Check the supply filter Check the supply pressure Check the inlet screen in the booster Check the power supply Check for an existing Input Signal Check for loose fi...