MENU ITEM FUNCTIONS

6

Control Value (

)

Displays the control input value in mA or Volts.

Option Value (

)

The Option Value 

 displays the current or voltage

value at the analog output option terminals.

Setup Menu (

)

See Table 2 and Figure 2 for setup options.

Tuning Menu (

)

See Configuring Menu 

 Tuning Coefficients,

Table 4 & Figure 2 for setup and PID Tuning Infor-
mation.

Analog Output Connection (

)

Sets the mode of operation for the Analog output option to

 or 

. Setting option to 

 configures the Output

Option to proportinally follow the output pressure in mA or
volts. The value is displayed in Option Value 

. Setting

option to 

 configures the Output Option to be used

as an independent keypad settable output signal in mA or
Volts and is displayed in the Option Value 

. See Table

5, Quick Setup Guide.

Output Pressure (

)

Displays the actual output pressure in the default
PSIG units. BAR and kPa units can be displayed
based on configuring (

) and (

) as discussed

in the Pressure Conversion section. See Table 6.

Setpoint (

)

Configuring the Model T7900/T7950 to control
output pressure 

, the Setpoint 

 menu

item on the Main menu displays the setpoint in
terms of output pressure. Selecting Setpoint 
with the control input channel 

 in Local 

mode causes the numberic characters to blink
unitl the value required is reached via the up/
down buttons and entered. Use Control Input

 configured in Remote 

 for controlling

the output pressure proportional to the signal
value at the control input channel terminals. This
is defined by the calibration relationship of 

,

, and 

 in the Configuration Menu 

.

Setpoint 

 displays the current pressure

setpoint value.

Control Input (

)

Control Input 

 configures the control input chan-

nel function. Setting 

 in Remote 

 mode, the

control input channel functions as setpoint control
to the Model T7900/7950. Control Input 

 set  to

LOCAL 

 chooses the Setpoint 

 using the

keypad to control the output pressure. In this mode,
the Model T7900/7950 control functions disregard
the analog input channel.

NOTE: The Control Input 

 and the

Analog Output Connection 

 have

four setting combinations that confi-
gure the Model T7900/7950 operation.
See Table 5, Quick Setup.

Calibration Menu (

)

See section 'Control Input Used as Setpoint
Control' , Table 3 & Figure 2 for setup options.

Look Ahead Function (

)

Using the Look Ahead 

 function can reduce the gain

error and enhance the Model T7900/T7950 response
characteristics in most linear control applications.  To

improve response characteristics, the Look-Ahead 
function predicts the required internal control correction
for a specific setpoint based on the characterizing
values 

 and 

.  To achieve optimum look-ahead

characteristics, the Configuration 

 menu items 

and 

 must be set with the Model T7900/T7950

operating with the supply pressures they will use in their
applications.

Pressure Unit Conversion (

) and (

)

The Model T7900/T7950 Output Pressure 

 can

display in any required pressure unit.  To convert to other
pressure units, set the values of menu items Numerator

 and Denominator 

.  Values entered in 

 and

 form a fractional conversion factor that converts the

base units of pressure (psig) in the Model T7900/T7950
into the required units.  The converted (new pressure)
unit is determined by the expression 

Converted Pressure

Unit

 = (pressure in psig) x (N/D).  Consult a conversion

table to obtain a conversion factor for the required units,
convert into a fractional form, and enter it into the Model
T7900/T7950 using 

 and 

.

Setup Menu (

) Operation

Control Units 

Sets control input units in mA 

 or volts 

 .

Values are input in the Configuration Menu 
as 

 and 

.

Analog Output Option Units (

)

To change the Analog Output Option Units  
between voltage 

 and current 

 enter the

appropriate unit on the 

 menu.

Summary of Contents for T79 Series

Page 1: ...RO PNEUMATIC TRANSDUCERS Analog Output Operation and Maintenance Instructions Software Version 3 45 and 3 46 SPECIFICATIONS Figure 2 Model T7950 Keypad Figure 1 Model T7900 Keypad Figure 3 Model T79xx Series Transducer Keypad Functions ...

Page 2: ...an internal electronic pressure sensor to achieve high accuracy pressure control Flexible configuration and PID tuning capability ensure that these pressure controllers can meet the most de manding air pressure control applications SPECIFICATIONS Model T7900 Model T7950 Electrical Supply voltage 11 24 VDC Power consumption Less than 4 watts Analog input Current mode input range 0 24 mA 35 mA maxim...

Page 3: ...entered on the setpoint which the unit does not respond Control Value Displays control input value Option Value Displays the feedback option output value Control Value 1 Sets the 0 Control Input value Control Value 2 Sets the 100 Control Input value Option 1 Sets the value of the current or voltage proportional to P1 Option 2 Sets the value of the current or voltage proportional to P2 2 Records th...

Page 4: ...Figure 2 Model T7950 Menu System 4 ...

Page 5: ...o Remote The Model T7900 T7950 control input channel is configured to accept an analog control signal to control the setpoint The Control Value displays the cur rent or voltage signal value at the control input terminals under all configurations The relationship between the control input signal and the output pressure is determined by and settings in the Configuration menu Output Control Analog Ou...

Page 6: ...unctions as setpoint control to the Model T7900 7950 Control Input set to LOCAL chooses the Setpoint using the keypad to control the output pressure In this mode the Model T7900 7950 control functions disregard the analog input channel NOTE The Control Input and the Analog Output Connection have four setting combinations that confi gure the Model T7900 7950 operation See Table 5 Quick Setup Calibr...

Page 7: ...tively mA 0 00 30 00 4 00 and 20 00 The Option Value will vary between 4 mA and 20 mA proportinally following the pressure output between 0 and 30 psig To achieve a reverse acting relationship set 20 00 and 4 00 or set 30 and 0 Look Ahead Items and Configuring Menu Tuning Coefficients The Model T7900 T7950 ships from the factory with nomi nal PID values Tune the PID coeffecients and for optimum pe...

Page 8: ...Kit 19715 2 3 To replace the solenoid valves in the Model T7950 install Service Kit 19715 1 4 For the Model T7900 install Service Kit 19375 1 5 To replace solenoid valves in the Model T7900 order quantity 2 of Part Number 290 IPI 001 2 Check the supply filter Check the supply pressure Check the inlet screen in the booster Check the power supply Check for an existing Input Signal Check for loose fi...