background image

7

The values of 

 and 

 are integers only and are

limited to the range of 1 to 9999.  The Model T7900/
T7950 ship from the factory with units of psig, BAR, or
kPa determined by the part number.  The Model T7900/
T7950 automatically determines the Output Pressure

 Decimal Point location 

 based on the maximum

Output Pressure 

 after the N/D conversion.

NOTE:

Unit

      N/            /D

 Comments

psig

      1

          1         psig = psig x 1

BAR

    100        1451      bar = psig x 0.0689

kPa         6895        1000      kPa = psig x 6.895
InHg

   5000        2456      InHg = psig x 2.036

Table 6.  Pressure Unit Values

The Setpoint 

 and Deadband 

 item

values display in terms of the converted
pressure units defined by the 

 and

conversion factor.

For more information about 

 and 

 values for

common pressure units, see Table 6.

Pressure Unit Conversion (

) and (

) cont.

Configuration Menu 

 Operation

Control Value used as Setpoint Control (

), (

),

(

) and (

)

The values in 

 and 

 set the relationship

between the control input signal and the output pressure.
Setpoint is displayed in terms of the output units. Config-
uring the control input for setpoint control, (

 = 

),

allows for the adjustment of the relationship between con-
trol input signal and the output.  To make the adjustment,
set the appropriate values in 

 and 

 on the

Configuration 

 menu.  When the control input signal

varies between the values in 

 and 

, the pressure

output varies proportionally between the values in 

 and

. For example:

 = mA, 

 = 0.00, 

 = 30.00, 

 =

4.00, and 

 = 20.00; Varying the control input

current between 4 mA and 2- mA varies the
pressure setpoint proportionally between 0 and
30 psig.

To achieve a reverse acting relationship, set 
= 20.00 and 

 = 4.00 or set 

 = 30 and 

= 0.

Option Value (

), (

)

Sets the analog value of 

 and 

 proportional to 

and 

, respectively.

 = mA, 

 = 0.00, 

 = 30.00, 

 =

4.00, and 

 = 20.00; The Option Value will

vary between 4 mA and 20 mA proportinally
following the pressure output between 0 and 30
psig.

To achieve a reverse acting relationship, set

= 20.00 and 

 = 4.00 or set 

 = 30 and

 = 0.

Look Ahead Items 

  and 

Configuring Menu 

 - Tuning Coefficients

The Model T7900/T7950 ships from the factory with nomi-
nal PID values.  Tune the PID coeffecients 

 and

 for optimum performance in the Tuning menu 

.

There are several PID optimization routines  used to adjust
the PID coefficients.  The following is a basic procedure
that works in most applications:

1.

Start with 

 = 1.00, 

 = 0, and 

 = 0.  

should be set to zero when optimizing PID.  Re-
turn 

 to the required value after optimizing PID.

2.

Increment 

 by 0.01 or other minimal value.

3.

Change the Setpoint 

 from 50% full-scale to

70% full-scale.  Change the setpoint back to 50%

4.

If the output stabilizes, go back to 1.

5.

If the output does not stabilize, measure the pe-
riod (in seconds) of the oscillations and go to step
6.

6.

Set 

 to 50% of the final unstable value previ-

ously identified.  Set 

 to the period of the os-

cillations.  Set 

 = 

 x 1/8.

To improve response characteristics , the Look  Ahead

 function predicts the required internal control correc-

tion for a specific setpoint based on the characterizing
values 

 and 

 must be enabled in the Setup

 Menu. The Look ahead 

 function is pressure sup-

ply sensitive requiring the pressure supply be set at the
expected operating value. To set 

 and 

, use the

following steps:

1.

Set the Deadband 

 on the Tuning 

menu to zero.

2.

Set the Setpoint 

 to a value between 10

and 20 % of the maximum operating range.

3.

Access the Configuration 

 menu. Scroll

through the menu until 

 displays. Press

the enter key, select 

. When 

 flashes

on the display, the new value is set.

4.

Repeat the procedure for 

 with the setpoint

between 70 and 100 % of the operating range

.

Option Value (

), (

) (cont)

Summary of Contents for T79 Series

Page 1: ...RO PNEUMATIC TRANSDUCERS Analog Output Operation and Maintenance Instructions Software Version 3 45 and 3 46 SPECIFICATIONS Figure 2 Model T7950 Keypad Figure 1 Model T7900 Keypad Figure 3 Model T79xx Series Transducer Keypad Functions ...

Page 2: ...an internal electronic pressure sensor to achieve high accuracy pressure control Flexible configuration and PID tuning capability ensure that these pressure controllers can meet the most de manding air pressure control applications SPECIFICATIONS Model T7900 Model T7950 Electrical Supply voltage 11 24 VDC Power consumption Less than 4 watts Analog input Current mode input range 0 24 mA 35 mA maxim...

Page 3: ...entered on the setpoint which the unit does not respond Control Value Displays control input value Option Value Displays the feedback option output value Control Value 1 Sets the 0 Control Input value Control Value 2 Sets the 100 Control Input value Option 1 Sets the value of the current or voltage proportional to P1 Option 2 Sets the value of the current or voltage proportional to P2 2 Records th...

Page 4: ...Figure 2 Model T7950 Menu System 4 ...

Page 5: ...o Remote The Model T7900 T7950 control input channel is configured to accept an analog control signal to control the setpoint The Control Value displays the cur rent or voltage signal value at the control input terminals under all configurations The relationship between the control input signal and the output pressure is determined by and settings in the Configuration menu Output Control Analog Ou...

Page 6: ...unctions as setpoint control to the Model T7900 7950 Control Input set to LOCAL chooses the Setpoint using the keypad to control the output pressure In this mode the Model T7900 7950 control functions disregard the analog input channel NOTE The Control Input and the Analog Output Connection have four setting combinations that confi gure the Model T7900 7950 operation See Table 5 Quick Setup Calibr...

Page 7: ...tively mA 0 00 30 00 4 00 and 20 00 The Option Value will vary between 4 mA and 20 mA proportinally following the pressure output between 0 and 30 psig To achieve a reverse acting relationship set 20 00 and 4 00 or set 30 and 0 Look Ahead Items and Configuring Menu Tuning Coefficients The Model T7900 T7950 ships from the factory with nomi nal PID values Tune the PID coeffecients and for optimum pe...

Page 8: ...Kit 19715 2 3 To replace the solenoid valves in the Model T7950 install Service Kit 19715 1 4 For the Model T7900 install Service Kit 19375 1 5 To replace solenoid valves in the Model T7900 order quantity 2 of Part Number 290 IPI 001 2 Check the supply filter Check the supply pressure Check the inlet screen in the booster Check the power supply Check for an existing Input Signal Check for loose fi...