6. Appendix
Table 6-1 Recommended Wire Diameters for Cables
Type
Cross-sectional
area
Different temperature conditions
AWG
mm
2
60
℃
75
℃
85
℃
90
℃
Wire type:
RUW, T, UF
Wire type:
RHW, RH
Wire type:
V, MI
Wire type:
TA, TBS, SA, AV
Rated Current (A)
14
2.08
20
20
20
20
12
3.31
25
25
30
30
10
5.26
30
35
40
40
8
8.36
40
50
55
55
6
13.3
55
65
70
75
4
21.1
70
85
95
95
3
26.7
85
100
110
110
2
33.6
95
115
125
130
1
42.4
110
130
145
150
0
53.5
125
150
165
170
00
67.4
145
175
190
195
000
85
165
200
215
225
0000
107
195
230
250
260