background image

Fig.5

CHIMNEY

Do not connect to a chimney serving another
appliance.

The stove is a radiant room heater and must be con-
nected to a chimney of the proper size and type.

The chimney must have  a diameter of at least 6”
(150mm).  It is best to connect to a chimney of the
same size, as connection to a larger size may result
in a somewhat less draught. If installation is into an
existing chimney then it must be sound and have no
cracks or other faults which might allow fumes into
the house.  Where the chimney diameter is greater
than 8” or the chimney is in need of repair the chim-
ney will need to be lined with a suitable approved
flue liner.  Minimum chimney height 15’ (4.5 meters)
from stove flue outlet measured vertically.  The stove
must be connected to a chimney with a minimum
continuous draft of 12 Pascals  poor draft conditions
will result in poor performance.

In adverse weather conditions, down drafts may be
experienced causing smoke or fumes to spill into the
room.  If this occurs shut the appliance down by
closing the air controls.  If the problem persists seek
the advice of a chimney sweep.

When installing a chimney care must be taken to
ensure the chimney/flue does not become a fire haz-
ard or a safety hazard where the flue pipe could be
touched.  Follow the requirements from the relevant
building regulations.

4

Fig.6

Fig.7

Any existing chimney must be clear of obstruction
and have been swept clean immediately before
installation of the stove. If the stove is fitted in place
of an open fire then the chimney should be swept
one month after installation to clear any soot falls
which may have occurred due to the difference in
combustion between the stove and the open fire.

A single wall metal fluepipe is suitable for connecting
the stove to the chimney but is not suitable for use
as the complete chimney. 

Blanking Plate

Flue Spigot

Flue Liner

Stainless Steel
Chimney Connector

Insulated Non-Combustible
Throat Seal

Non-Combustible 
Floor

Flue Liner

Stainless Steel
Chimney Connector

Non-Combustible 
Floor

Insulated Non-Combustible
Throat Seal

Summary of Contents for Dunmore

Page 1: ...nfirm persons should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled When using the stove in situations...

Page 2: ...nt 7 10 CO Alarm 8 11 Location 9 12 Floor Protection 9 13 Flue Locations 9 14 Handover 9 15 Technical Data 10 16 Specification 10 17 Installation Check list 11 18 Operating Instructions 12 19 Importan...

Page 3: ...tove care should be taken to avoid the possibility of personal injury IMPORTANT WARNING This stove must not be installed into a chimney that serves any other heating appliance 2 The complete installat...

Page 4: ...Fig 4 FLUE EXIT TOP REAR The stove is not designed to allow the chimney be cleaned through the stove A means must be provid ed to clean the chimney such as a soot box access door in the flue for clea...

Page 5: ...smoke or fumes to spill into the room If this occurs shut the appliance down by closing the air controls If the problem persists seek the advice of a chimney sweep When installing a chimney care must...

Page 6: ...epipe should not exceed 45o 90o bends should not be used Fig 8 Fig 9 Combustible material should not be located where the heat dissipating through the walls of fireplaces or flues could ignite it Ther...

Page 7: ...Fig 10 Fig 11 Fig 12 Fig 13 Fig 14 Fig 15 6 CLEARANCE TO COMBUSTIBLES CORNER INSTALLATION ALCOVE INSTALLATION FIREPLACE INSTALLATION FLUE CLEARANCES MINIMUM COMBUSTIBLE ALCOVE MANTLE CLEARANCE...

Page 8: ...s or rooms containing a shower Air vents traversing cavity walls should include a continuous duct across the cavity The duct should be installed in such a manner as not to impair the weather resistanc...

Page 9: ...2 and from the alarm manufac turers instructions Provision of an alarm must not be considered a substitute for either installing the appliance correctly or ensuring regular servicing and maintenance o...

Page 10: ...ls See Fig 16 FLUE LOCATIONS Flue outlet to suit 150mm 6 internal diameter flue pipe Fig 17 9 Fig 16 HANDOVER On completion of the installation allow a suitable period of time for any fire cement and...

Page 11: ...ow 6 6 g s Flue Gas Temperature at Nominal Output 364oC Gross Weight 130kgs Flue Outlet 150mm Flue Draught 12 Pascals Log Size 370mm WARNING DO NOT OBSTRUCT PRIMARY AIR SUPPLY TO THE STOVE SPECIFICATI...

Page 12: ...chimney serving this appliance should not serve any other appliance 6 Access should be provided to the chimney serving the appliance to allow for cleaning Location 7 Clearance to combustible material...

Page 13: ...eriod of time after use Children aged or infirm persons should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thorough l...

Page 14: ...e required heat output 10 To shut the fire down do not add fuel make sure that the firedoor is properly closed and that the primary and secondary air controls are all in the closed position Cutting of...

Page 15: ...from the heater at all times Operate the stove only with the fuelling door closed except for re fuelling WARNING Properly installed vented operated and main tained this stove will not emit fumes into...

Page 16: ...ensuring a proper seal is achieved NOTE Where the chimney is believed to have served an open fire installation it is possible that the higher flue gas temperature from a closed appliance may loosen d...

Page 17: ...a long time It is best to clean the glass when it is thoroughly cooled SUMMER SHUTDOWN For summer shutdown of the stove ensure all ashes have been cleaned from the ash compartment and that the air con...

Page 18: ...W 1 LEG 2 FRONT 3 SIDE PANEL NO LUGS 4 FLUE BLANKING PLATE 5 FLUE OUTLET COLLAR 6 BACK PANEL 7 HOB 8 SPIN VALVE 9 FIRE DOOR 10 ASHTRAY 11 INTERMEDIATE TOP AIR BAFFLE 12 ASHPAN 13 SEALING PLATE 14 DEFL...

Page 19: ...Manufactured by Waterford Stanley Ltd Unit 210 IDA Industrial Estate Cork Road Waterford Ireland Tel 051 302300 Fax 051 302315 DP 140207 N00594AXX 18...

Reviews: