The next parameter displayed
shows the “bypass input
voltage acceptable window”
setting. The voltage window can
be set to “Lo” (184-260Vac) or
“Hi” (195-260Vac), which is
shown below.
To change the settings, depress
the “Previous Page/Change
Setting” button. To change to the
alternate setting, press the but-
ton again. All setting changes
will be saved when prompted at
the end of the parameter
sequence.
Depress the “Next Page” button.
The next parameter displayed
shows the acceptable input
frequency window. The window
can be set to +/-3Hz (shown), or
+/-1Hz (not shown).
To change the settings, depress
the “Previous Page/Change
Setting” button. To change to the
alternate setting, press the but-
ton again. All setting changes
will be saved when prompted at
the end of the parameter
sequence.
Depress the “Next Page” button.
The next parameter display is
the inverter output voltage
setting. The inverter output volt-
age can be set to 200Vac (not
shown), 208 OR 220Vac (shown),
230Vac (not shown) or 240Vac
(not shown).
To change the settings, depress
the “Previous Page/Change
Setting” button. To change to
another voltage setting, repeat
pressing the button until the
desired voltage is
displayed. All setting changes
will be saved when prompted at
the end of the parameter
sequence.
Depress the “Next Page” button
and go to the next page.