Installation & User Manual Falcon Electric, Inc.
FN2 Series OM480051 Rev.: C 32
Bypass Mode
7. Verify the UPS is on and operating in Online Mode.
a. Press the Off button for approximately 5 seconds, UPS will emit 2 beeps.
b. UPS is in Bypass Mode
i. Display will indicate as shown in Figure B.
c. Press the Off button for approximately 5 seconds, UPS will emit 2 beeps and
return to Online Mode operation.
Maintenance Bypass Switch (MBS)
WARNING: DO NOT PLACE THE MAINTENANCE BYPASS SWITCH (MBS) IN THE
BYPASS POSITION WHILE THE UPS IS OPERATING IN ONLINE MODE. THE FOLLOWING
PROCEDURE MUST BE PERFORMED BEFORE USING THE MAINTENANCE BYPASS
SWITCH. FAILURE TO FOLLOW THIS PROCEDURE WILL RESULT IN DAMAGE TO THE
UPS OR CONNECTED EQUIPMENT.
8. Press the Off button for approximately 5 seconds, UPS will emit 2 beeps.
a. UPS is in Bypass Mode
i. Display will indicate as shown in Figure B.
b. Locate and remove the MBS cover.
c. Turn the MBS knob clockwise to the Bypass position.
i. The UPS load is now connected directly to utility power through the MBS.
The UPS input breaker may now be turned off.
9. To return to Online Mode operation, turn on input circuit breaker.
a. Display will indicate as shown in Figure B.
b. Turn MBS knob counterclockwise
to the “INV” (Inverter) position.
c. Reinstall MBS cover.
d. Press the on button for approximately 3 seconds, UPS will emit 2 beeps.
i. UPS will perform power on self-test, if passed UPS will return to normal
operation.
Summary of Contents for FN2 Series
Page 2: ......
Page 12: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev C 12 Accessories Kit...
Page 26: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev C 26 I1 J K L M N...
Page 27: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev C 27 O O1 P O2...
Page 29: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev C 29 S2 T U V1 V2 V3...
Page 39: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev C 39...