Installation & User Manual Falcon Electric, Inc.
FN2 Series OM480051 Rev.: C 35
Condition
Error Code
Solution
Red LED
(UPS Fault)
Er05, Low◄ & Fault ◄
Verify batteries are all connected
properly.
Replace battery packs.
Er06, Er10, Er12,
Er28 &
If CB3 is tripped, turn off the UPS and
keep the MBS at INV position before
pressing CB3. Disconnect load and
restart UPS. After error clears, reconnect
load.
EPO
Remove the short circuit at the EPO
terminal then restart UPS.
Er11, Er33
Remove any objects blocking the
ventilation holes.
Er14
Replace cooling fan.
Er15
If UPS is in CVCF mode, you must
restart the UPS.
Er16, Er17, Er27
All the parameters except ID Number in
a parallel UPS must be the same. Please
reference parallel procedure to
reprogram.
Er21
Disconnect and reconnect the RJ45
connector or set UPS with ID=1.
Er24
Bypass voltage present in CF50 / CF60
constant mode. Please contact Falcon
Electric, Inc. for resolution.
Er**
Other error codes, contact Falcon
Service Department for further
assistance.