60
Chapter 5 Managing USHA/UPS via SNMP
Setting SNMP parameters in USHA
If you intend to manage your USHA/UPS via SNMP NMS (Network Management station), you may
want to customize some of the SNMP settings (such as System Name, System Contact and System
Location and so on).
Before using USHA in SNMP environment, the IP address and gateway must be properly
configured. Please refer to Chapter 2 for the details.
SNMP Access Control Setting
Because of the USHA supports SNMP network protocol, you can use SNMP NMS to manage UPS
through the network. The IP address of the workstation must be set up in the USHA write access
table to prevent unauthorized users from configuring USHA via HTTP or SNMP protocols.
Note: If you do not enter the IP address of the workstation to the Access Control Table (via
Serial Port or Telnet) or the SNMP/HTTP Access Control (via Web Browser) in USHA, the SNMP
NMS can only view the UPS status; it will not be able to perform any configuration on
USHA/UPS. (See Pg. 14 SNMP Control Table and Pg. 22 SNMPv3 USM Table for details.)
SNMP Trap Receivers Setting
See Pg. 21 SNMP Trap Receivers for details.
Set up SNMP Manager Software
1.
Add the MIB file of USHA from the USHA CD-ROM to the MIB database of the SNMP
manager.
2.
Search the USHA equipment in the network
3.
To access the USHA SNMP agent, use ‘public’ for the GET community string and the
Read/Write password (default is
admin
) for the SET community string.
GET Community string: public
SET Community string: admin
For more information, see the MIB file on the USHA CD-ROM.