UPS Shutdown during Power Crisis
USHA responds to seven different kinds of UPS shutdown events and it will take appropriate
action to protect your information in your server. Go to the UPS Shutdown in the UPS
Management menu. Login the web user interface as an administrator identity. Configure the
UPS Shutdown table to meet your need. Click the Set Value button when finished.
Status:
UPS Turn Off (default value)
Delay (Min):
10
(default value)
1
st
Warning (Sec)
30
(default value)
Warning Interval (sec)
30
(default value)
UPS Shutdown Delay (Sec): 180
(default value)
AC failed at
22:20:00
22 : 20 : 00 22 :30 :00 22 : 33 : 00
Client’s local shutdown delay (Sec):120
(default value)
22 : 20 : 00 22 : 32 :00
UPS ON
UPS SLEEP
UPS OFF
Client ON
Client OFF