4.11 3 to 6kVA System Installation Wiring Diagram (single rackmount UPS system)
4.12 3 to 6kVA System Installation Wiring Diagram (typical multiple parallel UPS units,
15
4.13 UPS & Transformer Modules Communications Bus Cabling
Use one UA88385 parallel communications bus cabling kit for each UPS to be connected to the system output trans-
former module or to paralleled UPS systems. Connect the supplied cables as shown below. Note the first and last con-
nectors on the first and last UPS are connected using the longer of the supplied cables. Switch on the termination resis-
tor dip switch next to the long cable. For the transformer module, daisy chain the cables from the UPS to the transformer
module in a similar manner using the communications connectors located on the transformer module rear panel.
Suggested UPS Output Panel & Circuit Breakers
UPS Output Panel = Square D P/NQQ12L125G (1 each)
Panel Master Circuit Breaker 120A = QQM110VH (1 Each)
Individual UPS Circuit Breakers
3kVA -- 20A Square D P/N QQ220VH
4kVA to 6kVA -- 30A Square D P/N QQ230VH
8kVA -- 50A Square D P/N QQ250VH
10kVA -- 60A Square D P/N QQ260VH