g. One Local Maintenance Bypass Switch. 

The switch is located on the transformer module rear panel

and provides a manual means of placing the UPS into bypass mode to allow for servicing to be performed on
the UPS and battery modules.

2.0 FN RACKMOUNT UPS CIRCUIT DESCRIPTIONS

Galvanically Isolated Output

The FN -2TXI output isolation transformer module provides a galvanically isolated, 120/240Vac, hardwire out-
put. To meet UL and code requirements, a dedicated electrical panel should be provided by your electrical
contractor or electrician. The FN -2TXI output configuration can be configured for a 120Vac, 208, 220, 230, or
240Vac output. It may also be configured for a dual voltage or 120/240Vac split-phase hardwire output. This
configuration allows for the use of a standard electrical panel and readily available branch rated circuit break-
ers It also simplifies the distribution to 240Vac and 120Vac loads.  The outputs of up to four FN -2TXI units
may be connected in parallel. Please refer to pages 12-13 of this manual for wiring details. 

Additionally, the FN galvanic output isolation in conjunction with a derived neutral greatly reduces common
mode noise and ground loops.

Input & Power Factor Correction

All FN rackmount models require a 2 wire plus ground type 208-240Vac power source, at 50 or 60Hz. Each
UPS module input must be connected to a dedicated circuit having a branch rated circuit breaker. If multiple
FN units are to be connected in parallel, care must be taken to verify the source electrical panel has enough
capacity. It must be rated to supply the total input power requirements of all FN Series units being connected,
including all optional extended battery chargers, in addition to any other circuits that may be connected to the
panel. Please have your electrical contractor review the FN datasheet located at the end of this manual and
perform a site survey several weeks in advance of the installation date.

While the FN Series UPS is operating from the utility power, it’s internal power factor correction circuit 
converts utility AC power into regulated DC power for inverter use. The circuit also corrects the input current
to maintain the phase relationships between both current and voltage sine waveforms. this also  minimize the
amount of current distortion that is reflected back to the utility line.  

DC/DC Converter

The DC/DC converter utilizes energy from the batteries and boosts up the DC voltage to a level required by
the inverter.  This allows the inverter to operate continuously at optimum efficiency and voltage. The converter
incorporates a patented circuit which reduces the amount of ripple current and EMI interference to the battery,
increasing the overall battery life.

DC/AC Inverter

In utility mode operation, the inverter utilizes the regulated DC output and converts it back into clean, 
regulated sinewave AC power.  When utility power fails, the inverter will receive its energy from the battery
through the DC/DC converter. In both modes of operation, the UPS inverter is online and continuously 
generates clean, regulated AC output power to the load. The IGBT, PWM inverter is of a very robust design
and produces a pure sinewave output with a +/-2% voltage regulation. Having a very low output impedance, it
can supply the high current demands of high inrush and non-linear loads. 

Summary of Contents for RACKMOUNT UPS PLUS FN3KRM-2

Page 1: ...2TXI FN8KRM 2 2TX 2TXI FN10KRM 2 2TX 2TXI FALCON Electric Inc 5116 Azusa Canyon Rd Irwindale California 91706 626 962 7770 Fax 626 962 7720 Email sales falconups com 2011 Falcon Electric Inc All right...

Page 2: ...ng Diagram Typical 16 4 15 External Battery Charger Option Installation 19 Chapter 5 Displays Controls 5 1 Control Button and LCD Locations 20 5 2 Control Button Operation 20 5 3 LED Display Modes 21...

Page 3: ...Display with Advanced Monitoring Remote Emergency Power Off REPO Option Input Power Factor Correction Wide Input Voltage Window Precision Output Voltage Regulation Superior Brownout Surge and Transie...

Page 4: ...the UPS in an indoor environment with an ambient temperature range of 32 F to 104 F 0 C to 40 C This UPS is designed for use with industrial scientific or data processing class equipment DO NOT USE TO...

Page 5: ...ration UPS control and programming are easily accessed using pushbuttons located adjacent to the LCD display FN rackmount UPS Battery and Transformer module rear panels have the following features and...

Page 6: ...upply the total input power requirements of all FN Series units being connected including all optional extended battery chargers in addition to any other circuits that may be connected to the panel Pl...

Page 7: ...mode The UPS batteries are being charged whenever the UPS is plugged in turned on and operating from utility power The internal UPS battery charger output is rated at 1 9 amps Static Bypass Function N...

Page 8: ...nstallation Kit 1 Software Interface Cable 1 Owner s Manual 1 Installation Kit FNITRM 2 Rackmount Output Transformer Module 1 Installation kit 2 UPS Communications Interface Cables NOTE If multiple FN...

Page 9: ...sure the maximum life of the batteries operation in an ambient temperature of 68 F to 77 F 20 C to 25 C is recommended OPERATION IN TEMPERATURES ABOVE 77 F 25 C WILL REDUCE BATTERY LIFE 5 The FN Serie...

Page 10: ...ck Screw Torque 20 inch pounds Required Branch Rated input circuit breaker 30A 50A with 3 external battery charger module options installed Required Branch Rated output circuit breaker 30A FN6KRM 2TXI...

Page 11: ...240Vac 3 500W split phase 3 wire plus ground 2 FN5KRM 2TXI Not N 1 7 000W N 1 3 500W 3 FN5KRM 2TXI Not N 1 10 500W N 1 7 000W 4 FN5KRM 2TXI Not N 1 14 000W N 1 10 500W 1 FN6KRM 2TXI Not N 1 Hardwire 1...

Page 12: ...4 5 FN 3kVA to 6kVA Rackmount System Rear Panel Overview 4 6 FN 8kVA to 10kVA Rackmount System Rear Panel Overview 12...

Page 13: ...4 7 3 to 6kVA Output Transformer Module Hardwire Terminal Block Wiring Details 13 4 8 3 to 6kVA UPS Module Hardwire Terminal Block Wiring Details...

Page 14: ...4 9 8 to 10kVA UPS Module Hardwire Terminal Block Wiring Details 4 10 8 to 10kVA Output Transformer Module Hardwire Terminal Block Wiring Details 14...

Page 15: ...nectors on the first and last UPS are connected using the longer of the supplied cables Switch on the termination resis tor dip switch next to the long cable For the transformer module daisy chain the...

Page 16: ......

Page 17: ...4 14 8 to 10kVA System Installation Wiring Diagram typical rackmount UPS system 17...

Page 18: ...nd CB2 on rear panel and leave the unit in bypass mode BPS 3 Press and hold the ON and Next Page button simultaneously until the unit beeps twice and enters programming mode 4 Using the Next Page butt...

Page 19: ...ption Installation Wiring Detail Typical UPS unit with optional FN6KBC 5A 2 5 Amp External Battery Charger Module FN6KBC 5A 2 Battery Charger Module Terminal Block Wiring Details Battery Charger Modul...

Page 20: ...r battery mode depressing this button will silence any audible alarms Off Bypass Button 1 When the UPS is operating in utility or battery mode depressing and holding this button until an audible beep...

Page 21: ...Programming Mode and prompted on the LCD display to SAVE settings pressing this button will save all changed parameters Utility AC Source 1 UPS Input Power Present LED Green Indicates utility power i...

Page 22: ...ay In the event of a utility loss that depletes that battery charge the Low Battery icon is displayed until the batteries have recharged to a reasonable level In the event of a complete battery discha...

Page 23: ...ng temperature is not too high Verify the UPS cooling fan operation Er12 Error code 12 indicates the UPS output is overloaded similar to error code 10 This could indicate the connected equipment excee...

Page 24: ...the following LCD display will be shown NOTE Always allow the UPS to charge its batteries for 8 hours prior to use 5 The UPS will now sequence up to on line mode and display the following Display A i...

Page 25: ...the UPS fails the self test FAIL is displayed alternately with an error code Please note the error code and contact Falcon Service The UPS is now turned on and in on line inverter mode Using an AC vol...

Page 26: ...y inverter or battery mode depress the Off button until the UPS sounds two audible beeps The UPS will switch to static bypass and turn off the inverter The LCD will display OFF or BPS The connected lo...

Page 27: ...tage Depress the Next Page button The r denotes the reading is for utility The arrow under the LINE indicates the reading is for the utility frequency Depress the Next Page button The b denotes the re...

Page 28: ...e battery icon indicates the reading is for the battery voltage Depress the Next Page button The degree C symbol indicates the reading is for the internal UPS temperature Depressing the Next Page butt...

Page 29: ...e alarm buzzer status It is shown here to be turned on If the Previous Page Change Setting button is pressed the audible alarm will be turned off Depressing the button again will turn the alarm back o...

Page 30: ...hown below Depress the Next Page button The next parameter displayed shows acceptable input frequency window The window can be set to 3Hz shown or 1Hz not shown Depress the Next Page button The next p...

Page 31: ...tage adjustment The adjustment can be set to 0 shown 1 1 2 2 3 or 3 not shown Depress the Next Page button The next parameter displayed shows the UPS unit address If only one UPS is being used the add...

Page 32: ...them down until the UPS sounds two beeps The audible alarm status parameter setting will be displayed 32 The audible alarm parameter settings cannot be set in this programming mode Refer to section 6...

Page 33: ...wn To change the settings depress the Previous Page Change Setting button To change to the alternate setting press the button again All setting changes will be saved when prompted at the end of the pa...

Page 34: ...z mode the UPS inverter output frequen cy will always be 60Hz Setting the UPS to a fixed or constant output frequency should be done when the input source is a generator To change between these settin...

Page 35: ...er displayed shows the UPS position when used in a parallel configuration The positions are 01 02 03 or 04 If only one UPS is being configured the position should be set to 01 as shown To change betwe...

Page 36: ...e the two phillips screws securing the upper and lower sides of the maintenance bypass security cover plate 3 On the rear of the transformer module turn the Maintenance Bypass Switch to Bypass The mai...

Page 37: ...P N UA88380 CAUTION The internal USHA SNMP HTTP AGENT device must be installed into the Advanced Communications Option Slot specified in this manual Do not attempt to install it in the contact closur...

Page 38: ...displayed on the LCD panel After removal of the EPO contact closure the UPS must be completely shut down and restarted to clear the EPO condition 7 4 Optional Communications Interface Board Details UA...

Page 39: ...LINUX 39 1 3 4 2 Pin 1 VCC 5V Pin 2 D Pin 3 D Pin 4 Ground 1 2 3 4 5 6 7 8 9 10 Pin 1 UPS on Bypass Pin 2 Utility Abnormal Pin 3 Utility Normal Pin 4 Inverter On Pin 5 Low Battery Pin 6 Abnormal Batt...

Page 40: ...it is recommended to connect the battery module and turn on the UPS for at least 24 hours every four to six months to ensure full recharging of the batteries This will pre vent excessive battery self...

Page 41: ...alleled The cable kit is shipped with each transformer module inside the shipping container The interface kit contains 1 daisy chain bus cable 3076 1 wrap around bus cable 3077 detailed installation i...

Page 42: ...teries Remove watches rings and other metal objects Use tools with insulated handles Do not lay tools or metal parts on top of batteries Do not attempt to alter any battery wiring or connectors Attemp...

Page 43: ...se the original shipping container and packing materials will likely result in the unit being received by Falcon with shipping damage Falcon Electric will not assume any responsibility for shipping da...

Page 44: ...de of Falcon s control such as fire accidents impacts iv normal wear and tear such as cleaning and replacement of batteries The warranty is null and void if i the product is used in conjunction with l...

Reviews: