CHAPTER 2
CHAPTER 2
INSTALLATION INSTRUCTIONS
General - Common for all models
1.
Verify the following is included in the UPS shipping carton:
(1) UPS, (1) Software Diskette(s) & Manual, (1) Owners Manual & (1) UPS/Computer
Cable.
2.
Verify the UPS unit is configured for the proper input/output voltage and frequency. This
information is stated on the nameplate label located on the rear or the side panel of the
unit. If any special input plug and output receptacle configurations were specified at the
time of order, verify for proper configuration.
3.
Set the output voltage and green mode switches located on the UPS rear panel for the
nominal UPS output voltage desired.
See the switch setting tables located on
page 5
.
In most cases the nominal UPS output voltage should be set to match the incoming utility
voltage. This will assure a close matching voltage in the event the UPS is placed on
bypass.
NOTE: Disregard the "ON" marking on the side of the actual dip switch
housing; use the tables in this manual or the silkscreen on the UPS rear panel only.
Dip switch 3 "enables" or "disables” the "Green Mode" function.
The UPS is shipped
from the factory with the switch set in the "disabled" position (up). If SW3 is switched
down or to the "enabled" position, the Green Mode function is activated. When the
load connected to the output of the UPS drops to under 10% of the full rated UPS output
for 30 seconds, the UPS is automatically placed into bypass and the inverter is turned off.
NO BATTERY BACKUP IS PROVIDED AFTER THE GREEN MODE HAS ACTIVATED.
Dip switch settings must be made while the UPS is turned off. Any changes made while
the UPS is turned on will not take effect until the UPS is turn off and back on again since
the switch settings are read by the microprocessor only during initial UPS power up
.
4.
To prevent accelerated battery discharge during shipment, this UPS was shipped with the
battery circuit breaker turned off. TURN THE BATTERY DISCONNECT CIRCUIT
BREAKER ON PRIOR TO TURNING ON THE UPS INPUT CIRCUIT BREAKER.
NEVER TURN THE BATTERY CIRCUIT BREAKER OFF WHILE THE UPS AC CIRCUIT
BREAKER IS TURNED ON AND OPERATING FROM THE UTILITY VOLTAGE, OR UPS
DAMAGE MAY RESULT. UPS MUST BE COMPLETELY SHUT DOWN PRIOR TO
DISABLING THE INTERNAL BATTERY SUPPLY.
In the event this UPS is to be turned off or stored for more than two weeks, the battery
circuit breaker must be turned to the off position to prevent battery discharge. If placed in
long-term storage, every four months the UPS must be plugged in and turned on for 24
hours to allow the batteries to recharge and prevent battery damage. Failure to follow
these procedures will invalidate your warranty.
CAUTION
CAUTION
4