2.2 Special Features
1. Our High Frequency Transformer-less technology and tower-convertible
form factor enables the UPS to be integrated into environments with space
constraints.
2. This UPS is equipped with fully digital control logic for greater functionality
and enhanced power protection. Digital signal processing (DSP) also
provides the UPS with powerful communication capability, which simplifies
remote control and monitoring.
3. Our wide input voltage tolerance of 90-150Vac allows under-voltage or
over-voltage correction without unnecessary battery drain and helps
extend battery life.
4. Our DC-start function ensures the start-up of the UPS even during power
outages.
5. Our smart battery management system maximizes overall battery life.
6. Our Active Power Factor Correction control function constantly maintains
the UPS input power factor at > 0.9 for superb energy efficiency.
7. Our Selectable Bypass input voltage tolerance (sensitivity low / high)
prevents under or over-voltage being supplied to the loads in bypass mode.
The selectable voltage ranges are (i) Bypass Sensitivity Low:
±
15% of
available output voltage setting and (ii) Bypass Sensitivity High:
±
10% of
available output voltage setting. For example, if the output voltage setting
is 120V, the Bypass Sensitivity Low range is 120Vac ±15%, i.e., 102 - 138
Vac.
8. The UPS provides numerous configurable output voltages to match
various system voltage requirements.
9. The UPS is designed to comply with various stringent international
standards for electromagnetic interference compatibility (EMC).