Battery Bank Installation Procedure
The battery modules have been designed to be placed on one side of the UPS as shown below.
1.
Visually inspect the battery module for any freight damage. Report damage to the
carrier and Falcon Electric immediately.
2.
Use the mounting feet to secure the unit and to prevent them from tipping over. One
additional set of mounting feet base extensions ships with each battery bank.
3.
Turn off the battery disconnect switch and connect the supplied battery bank cable to
the UPS connector located on the rear of the battery bank. Next connect the other end
of the cable to the battery bank connector located on the rear of the UPS as shown.
4.
Turn on the battery disconnect switches located on the back on the rear of the
battery bank(s).
15